journal article·2026-06

Corrosion management of condenser tubes in power generating station – field trail

Chidambaram Subramanian

Publisher page

Abstract

This article presents the corrosion monitoring of condenser tubes in power generating station. The cooling water is used for condensing low pressure (LP) steam and several additives are systematically injected into cooling water for corrosion protection without affecting the performance of anti-scalant. Firstly, 10 ppm of mixture consisting of organophosphonate + HEDP (1-hydroxyethylidine-1, 1-diphosphonic acid) + zinc, 2 ppm of bio-dispersant and 6 ppm of mixture consist orthophosphate + zinc were dosed into cooling water. It was referred as mixture 1. Secondly, 5 ppm of pyrophosphate was further injected into cooling water in addition to mixture 1 referred as mixture 2. Lastly, 10 ppm of polymeric dispersant was dosed subsequently into cooling water referred as mixture 3. All three different conditions obtained from three mixtures were taken as plant trail for 1 month separately to establish the field condenser performance to maintain scale deposition and to prevent tubes against internal water corrosion. An addition of polymer dispersant showed improved corrosion protection due to formation of crystalline calcium phosphate layer which could act as anti-scalant as well as anti-corrosive layer. Moreover, heat transfer had been achieved by presence of co-polymer. The field trail of selected additive injection and examination of formed scales deposits may provide good insights on corrosion management of actual cooling water system.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Advanced Power Generation Technologies · Hybrid Renewable Energy Systems · Solar Thermal and Photovoltaic Systems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Central Mechanical Engineering Research Institute-CSIR

References (27)

Show source-provided references
1. 10.1016/j.mtcomm.2023.10699510.1016/j.mtcomm.2023.106995 ↗
2. 10.1016/j.jpse.2021.05.00110.1016/j.jpse.2021.05.001 ↗
3. 10.1016/j.conbuildmat.2024.13550910.1016/j.conbuildmat.2024.135509 ↗
4. 10.1016/j.engfailanal.2021.10598310.1016/j.engfailanal.2021.105983 ↗
5. 10.1179/147842210X1269514903393610.1179/147842210X12695149033936 ↗
6. 10.1016/j.est.2023.10700510.1016/j.est.2023.107005 ↗
7. 10.1002/prs.1221310.1002/prs.12213 ↗
8. 10.1179/1743278214Y.000000022810.1179/1743278214Y.0000000228 ↗
9. 10.1016/j.engfailanal.2020.10464310.1016/j.engfailanal.2020.104643 ↗
10. 10.1016/j.engfailanal.2022.10624510.1016/j.engfailanal.2022.106245 ↗
11. 10.1016/j.engfailanal.2024.10866410.1016/j.engfailanal.2024.108664 ↗
12. 10.1016/j.engfailanal.2021.10577310.1016/j.engfailanal.2021.105773 ↗
13. Tang Y, Xiang S, Wang J, et al. Study on the erosion patterns of high-strength injection-production strings under alternating operating conditions in gas storage reservoirs. Phys Fluids 2025; 37. https://doi.org/10.1063/5.0257696
14. 10.1061/JGGEFK.GTENG-1197610.1061/JGGEFK.GTENG-11976 ↗
15. 10.1016/j.engfailanal.2018.06.00810.1016/j.engfailanal.2018.06.008 ↗
16. 10.1080/1478422X.2023.218863710.1080/1478422X.2023.2188637 ↗
17. Chidambaram S. Thermal damage of sulfur processed chamber under Claus operating reaction conditions – a case study. Case Stud Constr Mater 2018; 8: 517–529. https://doi.org/10.1016/j.cscm.2018.04.005
18. 10.1016/j.engfailanal.2022.10620010.1016/j.engfailanal.2022.106200 ↗
19. 10.1080/1478422X.2019.166300710.1080/1478422X.2019.1663007 ↗
20. 10.1007/s11668-024-02015-410.1007/s11668-024-02015-4 ↗
21. 10.1007/BF0024373710.1007/BF00243737 ↗
22. Buentello KE, Kessler SM, May RC, et al. Method for controlling scale formation and deposition in aqueous systems. USP 2003: 6641754B2
23. 10.1016/j.desal.2024.11763910.1016/j.desal.2024.117639 ↗
24. 10.1016/B978-0-12-822896-8.00033-910.1016/B978-0-12-822896-8.00033-9 ↗
25. 10.1039/C9EW01036J10.1039/C9EW01036J ↗
26. 10.5004/dwt.2019.2418810.5004/dwt.2019.24188 ↗
27. 10.1080/1478422X.2020.186073010.1080/1478422X.2020.1860730 ↗