journal article·2014-07

Contact-based corrosion mechanism leading to copper sulphide deposition on insulating paper used in oil-immersed electrical power equipment

Marco Facciotti, Pedro S. Amaro, Alex F. Holt, Richard C.D. Brown, Paul L. Lewin, James A. Pilgrim, Gordon Wilson, Paul N. Jarman

Corrosion Science· Volume 84
Publisher page

Abstract

XPS and EDX were used to study CuxS deposition in Kraft insulating paper obtained from ageing paper samples in contact with a copper sheet, in mineral oil containing dibenzyl disulphide (DBDS). Qualitative and quantitative evidence of CuxS were obtained from bulk and surface analyses of insulating paper provided by the different depth resolution of the techniques used. The influence of [DBDS], oxygen, time, and Cu-paper contact upon the formation and mobilisation of CuxS were studied. A contact-based mechanism to explain CuxS contamination on paper and its displacement was proposed. The role of O2 in enhancing CuxS displacement was also investigated.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Corrosion Behavior and Inhibition · Electrodeposition and Electroless Coatings · Extraction and Separation Processes

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (25)

Show source-provided references
1. Heathcote · 2007
2. P. Jarman, Z. Wang, Q. Zhong, T. Ishak, End-of-life modelling for power transformers in aged power system networks, in: CIGRE 2009 6th Southern Africa Regional Conference, 2009.
3. Field studies of corrosion behaviour of copper alloys in natural seawater10.1016/j.corsci.2013.07.019 ↗
4. The corrosion of metals in contact with ester oils at temperatures up to 200°C10.1016/0010-938X(94)90037-X ↗
5. Factors affecting the dissolution of copper in transformer oils10.1002/ls.63 ↗
6. Corrosion mechanism of copper in palm biodiesel10.1016/j.corsci.2012.10.006 ↗
7. Laboratory scale investigation into the corrosion of copper in a sulphur-containing environment10.1016/j.corsci.2011.05.016 ↗
8. Research on influencing factors of corrosive sulfur attacking copper in insulating oil and prevention10.1002/tee.21894 ↗
9. Corrosive sulfur in insulating oils: its detection and correlated power apparatus failures10.1109/TPWRD.2007.911121 ↗
10. Corrosive sulfur effects in transformer oils and remedial procedures10.1109/TDEI.2009.5361586 ↗
11. Degradation of the insulating system of power transformers by copper sulfide deposition: influence of oil oxidation and presence of metal passivator10.1021/ie1013458 ↗
12. Corrosive sulfur induced failures in oil-filled electrical power transformers and shunt reactors10.1109/TPWRD.2008.2005369 ↗
13. Determination of copper in liquid and solid insulation for large electrical equipment by ICP-OES. Application to copper contamination assessment in power transformers10.1016/j.talanta.2012.07.009 ↗
14. M. Dahlund, I. Atanasova-Höhlein, R. Maina, N. Dominelli, T. Ohnstad, T. Amimoto, C. Claiborne, M.-H. Ese, J. Lukic, V. Mezhvynskiy, Ch. Perrier, P. Smith, J. Tanimura, CIGRE WG A2–32 Copper sulphide in transformer insulation Final, Report, 2009.
15. Duration and mechanism for suppressive effect of triazole-based passivators on copper-sulfide deposition on insulating paper10.1109/TDEI.2009.4784575 ↗
16. L. Lewand, S. Reed, Destruction of Dibenzyl Disulfide in Transformer Oil, in: 75th Annual International Doble Client Conference, 2008, pp. 1–20.
17. Highly sensitive detection method of dibenzyl disulfide and the elucidation of the mechanism10.1109/TDEI.2009.4815186 ↗
18. Role of dissolved copper and oxygen on copper sulfide generation in insulating oil10.1109/TDEI.2009.5293957 ↗
19. Investigation of Copper corrosion in transformer oil
20. Effect of DBDS concentration and heating duration on copper sulfide formation in oil-immersed transformer insulation10.1109/TDEI.2011.6118625 ↗
21. XPS Observations of the diffusion of copper through the paper layers used to insulate transformers
22. Experimental study of a passivated oil corrosiveness, after depletion of the passivator10.1109/MEI.2009.5313707 ↗
23. IEC TC 10, Insulating liquids, Test method for detection of potentially corrosive sulphur in used and unused insulating oil EN 62535 (2011).
24. A.R. West, Basic solid state chemistry, John Wiley & Sons Ltd., 1991.
25. P.S. Amaro, M. Facciotti, A.F. Holt, J.A. Pilgrim, P.L. Lewin, R.C.D. Brown, G. Wilson, P.N. Jarman, Tracking Copper Sulfide Formation in Corrosive Transformer Oil, in: CEIDP, 2013.10.1109/CEIDP.2013.6747071 ↗