Abstract Consideration is given, in this paper, to the accurate numerical solution of transient flows in relatively long pipelines caused by the water hammer phenomenon. The governing equations for such flows are a set of two coupled non-linear hyperbolic partial differential equations where the friction factor is a very important parameter. In these equations, the gravity force is introduced to take into account the pipeline inclination. The mathematical equations are solved in the time domain by the method of characteristics using linear integration. To reproduce correctly the transient flow, very small time increments were used in the constructed computer program. This program permits to get some systematic indications on the evolution and the damping of the pressure head waves due to a fast closing valve at the downstream end of a long pipeline. The study shows that results are different from those of short pipelines and small viscous fluids. To check the validity of the numerical model, computed results have been successfully compared with those found in the relevant literature. These results show that the gravity lift may have an important effect on the maximum pressures, which may become very important near the valve and cause failure of the pipeline especially in presence of defect. The safety factor, computed at equidistant sections of the line, determines the distance between the reservoir and the defect from which the failure may happen. For the considered application, results show that the pipeline is safe near the supply upstream tank.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Water Systems and Optimization · Geotechnical Engineering and Underground Structures · Flow Measurement and Analysis
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (19)
Show source-provided references
1. Chaudhry · 1979
2. Streeter · 1967
3. Wylie · 1978
4. Wylie · 1993
5. Abott · 1966
6. Du Coup de Bélier en Hydraulique Au Coup de Foudre en Électricité
7. Fröberg · 1979
8. Pluvinage · 2001
9. Hosseini SA. Assessment of crack in corrosion defects in natural gas transmission pipelines, University.
10. SINTAP: Structural Integrity Assessment Procedure. Final Report E-U project, Brite Euram Programme, Bruxelle; 1999 [BE95-1462].
11. Water hammer effects on a gray cast iron water network after adding pumps10.1016/j.engfailanal.2014.04.023 ↗
12. Evaluation of the effect of corrosion defect on the structural integrity of X52 gas pipelines using SINTAP procedure and notch theory10.1016/j.ijpvp.2006.10.005 ↗
13. Pipeline failure due to water hammer effects10.1111/j.1460-2695.2006.01071.x ↗
14. Failure of grey cast iron water pipe due to resonance phenomenon10.1016/j.engfailanal.2012.06.009 ↗
15. Theoretical and numerical aspects of the volumetric approach for fatigue life prediction in notched components10.1016/S0142-1123(02)00040-3 ↗
16. Experimental and computed stress distribution ahead of a notch in a pressure vessel: application of t-stress conception10.1016/j.commatsci.2012.01.029 ↗
17. Experimental and numerical study of stress–strain state of pressurised cylindrical shells with external defects10.1016/j.engfailanal.2009.09.011 ↗
18. Failure of small diameter cast iron pipes10.1016/S1462-0758(02)00004-3 ↗
19. Zienkiewicz · 1988