Abstract

Abstract For approximately one year a frequent failure of coupling parts was observed after the successful retrofitting and operation of the motors of the cooling towers (CTs) fans with variable frequency drives (VFDs) at the airport site. The technician detected a powder underneath the coupling, which contained particles of rubber sleeve. A thorough investigation showed that the VFDs' configurations were not in accordance with VFDs Company's schematic control layout. Moreover, the CTs' leaving water temperature sensor goes directly to the building management system (BMS) and then to VFDs controls panels. Subsequently, any fault in the BMS control has direct effect on the temperature sensor signal to the VFDs controller. Recommendations were given to the client to replace the existing VFDs with advanced VFDs, since the existing electrical components of VFDs panels, such as the capacitors, transistors, and electrical wiring, are considered outdated according to their limited lifespan. Moreover, it was suggested to install a temperature sensing probe in the CTs' leaving common water header to the VFDs panels directly to avoid any faults from the BMS.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Advanced Machining and Optimization Techniques · Non-Destructive Testing Techniques · Power Transformer Diagnostics and Insulation

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (16)

Show source-provided references
1. Variable Frequency Drive · 2005
2. Montgomery · 2008
3. Variable frequency drives: operation and application with evaporative cooling equipment
4. A temperature control system for water cooling towers based on variable speed drives
5. Practical aspects regarding implementation of variable speed drives in cooling tower fans
6. ASHRAE · 2008
7. McquistonFayes · 1982
8. Adams · 1991
9. Energy savings of variable speed motors
10. Cooling tower technology
11. Torsional vibration problem with motor/ID fan system due to PWM variable frequency drive
12. Energy conservation improvement and ON–OFF switch times reduction for an existing VFD-fan-based cooling tower10.1016/j.apenergy.2015.05.025 ↗
13. Optimal control development for chilled water plants using a quadratic representation10.1016/S0378-7788(00)00119-5 ↗
14. Failure analysis of cooling fan gearbox10.1016/j.engfailanal.2011.11.009 ↗
15. Early fault diagnosis of bearing and stator faults of the single-phase induction motor using acoustic signals10.1016/j.measurement.2017.08.036 ↗