Summary Electrical cable trays are used in large quantities in nuclear power plants (NPPs) and are one of the main potential sources of fire. A malfunction of electrical equipment due to thermal stress for instance may lead to the loss of important safety functions of the NPPs. The investigation of such fires in a confined and mechanically ventilated enclosure has been scarce up to now and limited to nuclear industry. In the scope of the OECD PRISME‐2 project, the Institut de Radioprotection et de Sûreté Nucléaire (IRSN) conducted more than a dozen fire tests involving horizontal electrical cable trays burning either in open atmosphere or inside mechanically ventilated compartments to investigate this topic. A semi‐empirical model of horizontal cable tray fires in a well‐confined and mechanically ventilated enclosure was developed. This model is partly based on the approach used in FLASH‐CAT and on experimental findings from IRSN cables fire tests. It was implemented in the two‐zone model SYLVIA. The major features of the compartment fire experiments could then be reproduced with acceptable error, except for combustion of unburned gases. The development of such a semi‐empirical model is a common practice in fire safety engineering concerned with complex solid fuels.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Fire dynamics and safety research · Combustion and Detonation Processes · Fire effects on ecosystems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Institut de Radioprotection et de Sûreté Nucléaire (IRSN) BP n°3 13115 St Paul‐Lez‐Durance Cedex France

References (36)

Show source-provided references
1. U.S. NRC · 1975
2. Sumitra PS · 1982
3. IEEE‐383‐1974Standard for type test of Class IE Electric Cables Filed Splices and Connections for Nuclear Generation Stations Institute of Electrical and Electronic Engineers.
4. 10.1002/fam.75610.1002/fam.756 ↗
5. McGrattan K. Lock A. Marsh N. Nyden M. Bareham S. Price M. Morgan A.B. Galaska M. Schenck K. Stroup D. 2012.Cable heat release ignition and spread in tray installations during fire (CHRISTIFIRE). Volume 1: Horizontal Trays NUREG/CR‐7010 U.S.NRC.
6. McGrattan K. Bereham S. 2013.Cable heat release ignition and spread in tray installations during fire (CHRISTIFIRE). Phase 2: Vertical Shafts and Corridors NUREG/CR‐7010 Vol. 2 U.S.NRC.
7. Keski‐Rahkonen O. Mangs J. Bertrand R. Röwekamp M. Fire induced damage to electrical cables and fire growth on cables EUROSAFE2002 Forum for nuclear safety Berlin.
8. Audouin L. Prétrel H. Zavaleta P. OECD PRISME 2 Fire Research Project (2011–2016) – Current Status and Perspectives 13thInternational Post‐Conference Seminar on Fire Safety in Nuclear Power Plants and Installations.
9. Zavaleta P · 2013 · p57
10. Zavaleta P · 2017 · 17
11. 10.1002/fam.245410.1002/fam.2454 ↗
12. ZavaletaP. Suard S. Audouin L. 2018 Cable tray fire tests with halogenated flame retardant cables in a confined and mechanically ventilated facility. Under submission to Fire and Materials.10.1002/fam.2717 ↗
13. Tewarson A · 1979
14. Electric Power Research Institute
15. Quintiere J · 2002
16. 10.1016/j.nucengdes.2017.08.03110.1016/j.nucengdes.2017.08.031 ↗
17. NUREG‐1805 2004.Fire Dynamics Tools (FDT) Quantitative Fire Hazard Analysis Methods for the U.S. Nuclear Regulatory Commission Fire Protection Program Volume 1.
18. Lee BT · 1985
19. Nowlen SP · 1989
20. 10.3801/IAFSS.FSS.3-68910.3801/IAFSS.FSS.3-689 ↗
21. 10.1007/s10694-015-0538-210.1007/s10694-015-0538-2 ↗
22. 10.1002/fam.212810.1002/fam.2128 ↗
23. 10.1002/fam.81004020210.1002/fam.810040202 ↗
24. Karlsson B · 2000
25. Quintiere JG · 2008
26. 10.13182/NT93-A3481910.13182/NT93-A34819 ↗
27. 10.1016/j.buildenv.2012.07.00710.1016/j.buildenv.2012.07.007 ↗
28. Dynamics of the fire plume
29. Hasemi Y · 1989 · 275
30. 10.3801/IAFSS.FSS.5-40310.3801/IAFSS.FSS.5-403 ↗
31. 10.3801/IAFSS.FSS.9-93110.3801/IAFSS.FSS.9-931 ↗
32. MangsJ.2013.Characterization tests on cables samples with cone calorimeter VTT‐R‐03467‐13 (private communication).
33. JCGM 100:2008(F) GUM 1995 Evaluation of measurement data—guide to the expression of uncertainty in measurement September2008.
34. HaminsA.andMcGrattanK. Verification and validation of selected fire models for nuclear power plant applications Volume 2: Experimental Uncertainty NUREG‐1824 EPRI 1011999 Final Report May2007.10.6028/NIST.IR.7338 ↗
35. 10.1016/j.firesaf.2012.05.00210.1016/j.firesaf.2012.05.002 ↗
36. Investigation Heat and Smoke Propagation Mechanisms in Multi‐Compartment Fire Scenarios Final Report of the PRISME project NEA/CSNI/R(2017)14 January2018.