Interaction of fire plume with inclined surface
Source abstract
Abstract
Abstract The fire plume interacting with an inclined surface was visualised and analysed using a modified positive–negative grid schlieren system combined with a CCD camera and computer system. The fire source was simulated by a gas burner with a fine perforated burning surface. This produced a fire of 1.0–3.0 kW uniformly across the surface. Isothermal and adiabatic surfaces were constructed as the inclined surface. Sequences of the schlieren images of the fire plumes were taken systematically at various inclination angles from 0 to 40°. The images clearly showed that the fire plumes bent toward the surface. Near the burner, both the flame and the buoyant flow attached to the surface, and there was a point at which the plume detached from the surface and rose at an angle to the surface. Two parameters were measured from the schlieren images to describe the fire plumes features. The first is the length of the fire plume attachment to the surface, the second is the angle between the main stream of the plume and the inclined surface. It was found that the plume attachment length started to increase sharply, when the inclination angle reached 24°. This acceleration in the plume attachment length was used to identify the critical inclination angle. Measurements of the temperature distribution in the fire plume were also carried out using K-type thermocouples. The effects of the surface conditions and of the fire heat release rate on the plume and the critical inclination angle are discussed.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Combustion and Detonation Processes · Evacuation and Crowd Dynamics
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (12)
Show source-provided references
1. Fennel D. Investigation into the King's Cross Fire. London, UK: HMSO, 1988.
2. Jagger SF, Willoughby DB, Beckett H, Bettis RJ, Moodie K. Fire at King's Cross Underground station, 18th November 1987, Part 17: further one-third scale fire growth tests. RLSD Incident Report No. IR/L/FR/88/37, 1988.
3. Moodie · J Fire Prot Eng · 1992 · 3 · 4910.1177/104239159100300202 ↗
4. Simcox S, Wilkes NS, Jones IP. Fire at King's Cross Underground station, 18th November 1987: numerical simulation of the buoyant flow and heat transfer. AERE-G 4677, Harwell, UK, 1988.
5. Smith · Fire Safety J · 1992 · 18 · 23110.1016/0379-7112(92)90017-7 ↗
6. Wu Y, Drysdale DD. Upward flame spread on inclined surfaces. HSE Contract 2527/R04.25, February 1996.
7. Atkinson · Fire Safety J · 1995 · 25 · 14110.1016/0379-7112(95)00039-9 ↗
8. Woodburn · Fire Safety J · 1998 · 31 · 14310.1016/S0379-7112(98)00004-6 ↗
9. Woodburn · Fire Safety J · 1998 · 31 · 16510.1016/S0379-7112(98)00003-4 ↗
10. Drysdale · Fire Safety J · 1992 · 18 · 24510.1016/0379-7112(92)90018-8 ↗
11. Ito, Kashiwagi. Combust Flame 1988;71:189–204.10.1016/0010-2180(88)90007-7 ↗
12. Burton · J Opt Soc · 1949 · 39