journal article·2012-11

Spray characterization measurements of a pendent fire sprinkler

Xiangyang Zhou, Stephen P. D’Aniello, Hong-Zeng Yu

Publisher page

Abstract

Abstract The spray patterns of a pendent fire sprinkler were characterized through experimental measurements in the near and far field of the sprinkler. A laser-based shadow-imaging system was used to measure the droplet size, velocity and number density in the spray. An array of pressure-transducer-equipped water collection tubes and containers provided a separate set of water volume flux measurements. A large-scale traverse was constructed to move the laser optics and water collection tubes and containers to the designated measurement locations. A pendent fire sprinkler with K-factor of 205 lpm/bar1/2 (14.2 gpm/psi1/2) was characterized at two discharge pressures 3.5 bar and 5.2 bar (50 and 75 psi). In the near field at 0.76 m from the sprinkler, measurements were performed in a spherical coordinate at different azimuthal and elevation angles with respect to the sprinkler deflector. In the far field, the sprays were mapped out in a 110° circular sector at 3.05 m and 4.57 m below the ceiling. The shadow-imaging based water flux measurements were verified by the measurements obtained from water collection containers. The measurements show that the spatial distributions of water volume flux, droplet size and velocity of sprinkler sprays are strongly influenced by the sprinkler frame arms and the configuration of sprinkler deflector’s tines and slots. For the purpose of fire protection analysis, empirical correlations were developed from the near-field measurements to prescribe the spray starting conditions for the numerical modeling of spray transport through fire plumes. The far-field measurements can be used to evaluate the spray transport calculations.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Fire effects on ecosystems · Fire Detection and Safety Systems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (9)

Show source-provided references
1. C. Yao, Extinguishing role of water sprinklers, Proceedings of Engineering Applications of Fire Technology Workshop, April 16–18, 1980, National Bureau of Standards, Gaithersburg, MD, pp. 51–88.
2. The reaction of a fire plume to a droplet spray10.1016/j.firesaf.2006.02.005 ↗
3. Experimental investigation of spray formation as affected by sprinkler geometry10.1016/j.firesaf.2011.01.003 ↗
4. H.Z. Yu, Investigation of spray patterns of selected sprinklers with the FMRC drop size measuring system, Proceedings of the First International Symposium on Fire Safety Science, Hemisphere Publishing Corp., 1986, pp. 1165–1176.10.3801/IAFSS.FSS.1-1165 ↗
5. Measurements of water density and droplet size distributions of selected ESFR sprinklers10.1177/104239159400600202 ↗
6. Phase doppler interferometry measurements in water spray produced by residential fire sprinklers10.1016/S0379-7112(01)00009-1 ↗
7. D.T. Sheppard, Spray Characteristics of Fire Sprinklers, NISTGCR 02-838, National Institute of Standards and Technology, Gaithersburg, MD, 2002.
8. A comprehensive methodology for characterizing sprinkler sprays10.1016/j.proci.2010.06.107 ↗
9. Drop sizing and depth-of-field correction in TV imaging10.1615/AtomizSpr.v4.i1.30 ↗