journal article·2012-11

Experimental evaluation of fire suppression characteristics of twin fluid water mist system

Meenakshi Gupta, R. Rajora, S. Sahai, R. Shankar, Anjan Ray, S.R. Kale

Publisher page

Abstract

Abstract This paper reports the results of experiments performed in a 1 m 3 chamber on suppression of n-heptane pool fires using fine water-mist (D V50 ∼23 μm) generated from air aspirating twin fluid nozzles in continuous and pulsed mode. The effect of pulsing duration (1.0–1.4 s ON/0–1.3 s OFF), fire size (5–12.5 kW) and pre-burn duration (10–30 s) was studied for air and nitrogen as the atomizing fluid. During these experiments, fire suppression time, quantity of water for suppression and temperatures in the chamber were recorded. Fire suppression performance index (FSPI) was developed as an indicative measure of fire suppression effectiveness. It was observed that the best FSPI was achieved for a pulsing cycle of 1.3 s ON and 1 s OFF. Nitrogen as atomizing medium for mist generation was found to be more effective for fire suppression by 30–50%. Increase in pre-burn duration and fire size was found to reduce suppression time due to larger heat available in the chamber. Fire suppression for larger fire size was achieved with 25–30% of the combustion heat absorbed by the mist, indicating important contribution to fire suppression by other processes such as oxygen dilution and inerting due to water vapour.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Combustion and Detonation Processes · Fire effects on ecosystems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (23)

Show source-provided references
1. Review of water mist fire suppression systems—fundamental studies
2. Fire suppression by water sprays10.1016/S0360-1285(99)00012-X ↗
3. Dynamics of water droplets in a counterflow field and their effect on flame extinction10.1016/S0010-2180(97)00355-6 ↗
4. Flame inhibition/suppression by water mist: Droplet size/surface area, flame structure, and flow residence time effects10.1016/j.proci.2006.08.065 ↗
5. Better use of water for fire suppression
6. R. Ananth, C.C. Ndubizu, F.W. Williams, Numerical model for water mist suppression of a solid plate in boundary layer flow in: 14th Annual International Halon Options Technical Working Conference (HOTWC), Albuquerque, NM, May 4–6, 2004.
7. Ultra-fine water mist extinction dynamics of a co-flow diffusion flame. Combust
8. J.R. Mawhinney, Characteristics of water mists for fire suppression in enclosures, in; International Conference on Water Mist Fire Suppression Systems, Sweden, 1993.
9. J.R. Mawhinney, P. Eng, Characteristics of water mists for fire suppression in enclosures, in: Halon Options Technical Working Conference, May 4th–6th, 2004.
10. V. Novozhilov, Fire suppression studies, Review paper BIBLID: 0354-9836, vol. 11, 2, 2007, pp. 161–180.10.2298/TSCI0702161N ↗
11. The effects of droplet size and injection orientation on water mist suppression of low and high boiling point liquid pool fires10.1080/00102200008947310 ↗
12. Mechanisms of extinction of liquid fuel fires with water sprays10.1016/S0010-2180(60)80026-0 ↗
13. G.G. Back, Full scale tests of water mist fire suppression systems for navy shipboard machinery spaces, in: Proceedings of the Fourth International Symposium on Fire Safety Science, 1996, pp. 435–444.10.21236/ADA306668 ↗
14. On water mist fire suppression mechanisms in a gaseous diffusion flame10.1016/S0379-7112(98)00007-1 ↗
15. Optimizing water-mist injection characteristics for suppression of coflow diffusion flames10.1016/S0082-0784(98)80143-4 ↗
16. Simulation of water mist suppression of small scale methanol liquid pool fires10.1016/S0379-7112(99)00028-4 ↗
17. An experimental and numerical study on fire suppression using a water mist in an enclosure10.1016/S0360-1323(03)00134-3 ↗
18. J.R. Mawhinney, B.Z. Dlugogorski, A.K. Kim, A closer look at the fire extinguishing properties of water mist, in: Proceedings of the Fourth International Symposium on Fire Safety Science, pp. 1994.10.3801/IAFSS.FSS.4-47 ↗
19. Effect on radiant heat transfer at the surface of a pool fire interacting with a water mist10.1115/1.4000185 ↗
20. Z. Liu, A.K. Kim, J.Z. Su, Improvement of efficacy of water mist in fire suppression by cycling discharges, in: 2nd International Conference on Fire Research and Engineering, Gaithersburg, MD, USA, 1997.
21. Z. Liu, A.K. Kim, J.Z. Su, The effect of air convection on the performance of water mist fire suppression systems, in: ASME Proceedings of the 7th AIAA/ASME Joint Thermo-physics and Heat Transfer Conference, vol. 1, June 1998, pp. 227–236.
22. Examination of the extinguishment performance of a water mist system using continuous and cycling discharges10.1023/A:1015453014065 ↗
23. C. Hinds Williams, Aerosol technology—properties, behavior and measurement of airborne particles, 2nd edition, A Wiley Sci. Publication, pp. 296–300.