Performance in fire of FRP-strengthened and insulated reinforced concrete columns
Source abstract
Abstract
This research investigates the fire performance of one circular and one square reinforced concrete column strengthened with a fibre reinforced polymer (FRP) wrap and covered with a unique supplemental fire protection system. An experimental full-scale fire resistance test was conducted at the National Research Council of Canada. The insulated and strengthened FRP wrapped columns were exposed to the ULC-S101 standard fire and both columns obtained fire endurance ratings of over 4 h. Details of the fire endurance experiment on both columns are described in this paper. Additionally, numerical models developed specifically for circular and square columns are validated against the experimental results.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Structural Behavior of Reinforced Concrete · Innovative concrete reinforcement materials · Fire effects on concrete materials
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (24)
Show source-provided references
1. FRPs for structural rehabilitation: a survey of recent progress10.1002/1528-2716(200004/06)2:2<133::AID-PSE16>3.0.CO;2-C ↗
2. A review of the present and future utilisation of FRP composites in the civil infrastructure with reference to their important in-service properties10.1016/j.conbuildmat.2010.04.062 ↗
3. ULC · 2007
4. ASTM · 2010
5. Fire endurance of fiber-reinforced polymer-confined concrete columns
6. Ershad Chowdhury, Behaviour of Fibre Reinforced Polymer Confined Reinforced Concrete Column Under Fire Condition, Ph.D. Thesis, Department of Civil Engineering Queen's University, Kingston, Ontario, Canada, 2009.
7. Composites for high temperatures10.1351/pac198860030287 ↗
8. ACI. ACI 440.2R-08: Guide for the Design and Construction of Externally Bonded Frp Systems for Strengthening Concrete Structures, Farmingtion Hills, Michigan, American Concrete Institute.
9. L.A. Bisby, Fire Behavior of FRP Reinforced or Confined Concrete, Ph.D. Thesis, Department of Civil Engineering Queen's University, Kingston, Ontario, Canada, 2003.
10. CSA · 2002
11. New facility to determine fire resistance of columns10.1139/l80-063 ↗
12. American Concrete Institute (ACI). Building Code Requirements for Structural Concrete. ACI 318, Farmington Hills, MI, 2005.
13. Modeling the behavior of fiber reinforced polymer-confined concrete columns exposed to fire10.1061/(ASCE)1090-0268(2005)9:1(15) ↗
14. E.U. Chowdhury, L.A. Bisby, M.F. Green, N. Bénichou, V.K.R. Kodur, Fire Behaviour of FRP Wrapped Square Reinforced Concrete Columns, CDCC 2007, Quebec City, Canada, 22–24 May.
15. T.T. Lie, Structural Fire Protection. American Society of Civil Engineers Manuals and Reports on Engineering Practice No. 78, ASCE, New York, NY, USA, 1992.10.1061/9780872628885 ↗
16. Fire endurance of fiber-reinforced polymer-confined concrete columns
17. Cengel · 1998
18. Bond strength of CFRP and steel bars in concrete at elevated temperature
19. L.T. Phan, High-strength concrete at high temperature—an overview, in: Utilization of High Strength/High Performance Concrete, Sixth International Symposium, Leipzig, Germany, V. 1, 2002.
20. Numerical modelling of two-way reinforced concrete slabs in fire10.1016/j.engstruct.2004.03.009 ↗
21. Microstructure of fire-damaged concrete-a case study10.1016/j.cemconcomp.2004.02.022 ↗
22. On the multiaxial behaviour of concrete exposed to high temperature10.1016/0029-5493(83)90023-7 ↗
23. Development and practical application of fire-resistant steel for buildings
24. Mechanical characterization of fibre FRP materials at high temperature10.1007/s10694-009-0116-6 ↗