Water mist suppression of a turbulent line fire
Source abstract
Abstract
Abstract The present study seeks to measure suppression effects in a canonical experimental configuration, featuring the exposure of a buoyant, turbulent, methane-fueled diffusion flame to a co-flowing oxidizer laden with a fine water mist (Sauter mean diameter of 6.6 µm). The carefully designed facility features well-characterized inlet and boundary conditions suitable for accurate representation in numerical simulations. Suppression performance is monitored via combustion efficiency (ηcomb), measured using species-based calorimetry techniques. As the mass fraction of water mist in the oxidizer ( Y w m o x ) is increased, visible flame emissions are reduced due to diminishing soot incandescence coupled with a reduction in visibility due to Mie scattering effects in the mist. Global flame extinction is observed at Y wm ext = 0.093 , a condition corresponding to 44% less water mass in the oxidizer than required for extinction due to dilution effects alone, suggesting that significant latent cooling effects contribute to the observed extinction limit. Despite visually observed suppression effects, η comb ≈ 1 across all tested Y w m o x , decreasing abruptly only at the extinction limit. Numerical simulations of the experiments are conducted using FireFOAM, an open source large eddy simulation solver incorporating a flame extinction model based on a critical Damkohler number and a flame reignition treatment based on a critical flame temperature. Though numerical results show qualitative agreement with the observed extinction behavior, the simulated extinction limit of Y wm ext = 0.20 significantly exceeds that measured in the experiment, but is itself consistent with an extinction limit due only to dilution effects.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Combustion and flame dynamics · Combustion and Detonation Processes
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (35)
Show source-provided references
1. H-Z Yu, J. Newman, Theory of fire extinguishment. In Arthur E Cote, editor, NFPA Fire Protection Handbook, pp. 79–92. National Fire Protection Association, 20th edition, 2008.
2. H. Shilling, B. Dlugogorski, E. Kennedy, Extinction of diffusion flames by ultrafine water mist doped with metal chlorides, in: Proceedings of the Sixth Australasian Heat and Mass Transfer Conference, AFTES, 1996, pp. 275–282.10.1615/978-1-56700-099-3.330 ↗
3. Numerical modeling of water mist suppression of methane-air diffusion flames10.1080/00102209808952019 ↗
4. Dynamics and suppression effectiveness of monodisperse water droplets in non-premixed counterflow flames10.1016/S0082-0784(00)80718-3 ↗
5. Extinction conditions of non-premixed flames with fine droplets of water and water/NaOH solutions10.1016/S0082-0784(00)80719-5 ↗
6. The quenching of laminar methane-air flames by water mists10.1016/S0010-2180(02)00351-6 ↗
7. C. Ndubizu, R. Ananth, F. Williams, Water mist suppression of PMMA boundary layer combustion - A comparison of NanoMist and spray nozzle performance. Technical Report NRL/MR/6180-04-8824, NRL, 2004.10.21236/ADA426605 ↗
8. R. Ananth, C. Ndubizu, F. Williams, A numerical model for water mist suppression of a solid plate in boundary layer flow, in: Halon Options Technical Working Conference, NMERI, 2004, pp. 1–10.
9. Flow behavior impact on the suppression effectiveness of sub-10- μm water drops in propane/air co-flow non-premixed flames10.1016/j.proci.2006.07.023 ↗
10. Ultra-fine water mist extinction dynamics of a co-flow diffusion flame10.1080/00102200802197569 ↗
11. Inhibition of counterflow methane/air diffusion flame by water mist with varying mist diameter10.1016/j.firesaf.2014.11.030 ↗
12. A computational and experimental study of ultra fine water mist as a total flooding agent10.1016/j.firesaf.2006.08.010 ↗
13. E. Blanchard, S. Desanghere, P. Boulet, Quantification of energy balance during fire suppression by water mist in a mid-scale test tunnel, in: Fire Safety Science‐Proceedings of the Tenth International Symposium, IAFSS, 2011, pp. 119-132.10.3801/IAFSS.FSS.10-119 ↗
14. Experimental and numerical study of pool fire suppression using water mist10.1016/j.firesaf.2014.05.003 ↗
15. Large eddy simulation of flame extinction in a turbulent line fire exposed to air-nitrogen co-flow10.1016/j.firesaf.2016.09.003 ↗
16. Large eddy simulation of suppression of turbulent line fires by base-injected water mist10.1016/j.proci.2016.06.058 ↗
17. Radiative emissions measurements from a buoyant, turbulent line flame under oxidizer-dilution quenching conditions10.1016/j.firesaf.2015.05.003 ↗
18. J. White, E. Link, A. Trouvé, P. Sunderland, A. Marshall, A general calorimetry framework for measurement of combustion efficiency in a suppressed turbulent line fire, Fire Saf. J. (2017) submitted for publication.10.1016/j.firesaf.2017.06.009 ↗
19. The IAPWS formulation 1995 for the thermodynamic properties of ordinary water substance for general and scientific use10.1063/1.1461829 ↗
20. FireFOAM. FM Global, 2016. URL 〈https://www.github.com/fireFoam-dev〉.
21. OpenFOAM. OpenFOAM Foundation, 2016. URL 〈http://www.openfoam.org〉.
22. A comparative study of subgrid scale models in homogeneous isotropic turbulence10.1063/1.869254 ↗
23. On mathematical modeling of turbulent combustion with special emphasis on soot formation and combustion10.1016/S0082-0784(77)80366-4 ↗
24. J. Chai, S. Patanka, Discrete-ordinates and finite-volume methods for radiation heat transfer. In Handbook of Numerical Heat Transfer, pp. 297–323. John Wiley & Sons, 2006.10.1002/9780470172599.ch9 ↗
25. Dynamics of water droplets in a counterflow field and their effect on flame extinction10.1016/S0010-2180(97)00355-6 ↗
26. N. Nordin, Complex chemistry modeling of diesel spray combustion. (Ph.D. thesis), Chalmers University of Technology, 2001.
27. Particle tracking in unstructured, arbitrary polyhedral meshes for use in CFD and molecular dynamics10.1002/cnm.1128 ↗
28. Lagrangian-Eulerian methods for multiphase flows10.1016/j.pecs.2012.10.003 ↗
29. Current status of droplet and liquid combustion10.1016/0360-1285(77)90012-0 ↗
30. Recent advances in droplet vaporization and combustion10.1016/0360-1285(82)90011-9 ↗
31. Soot inception in a methane/air diffusion flame as characterized by detailed species profiles10.1016/0010-2180(85)90143-9 ↗
32. The effect of flame structure on soot-particle inception in diffusion flames10.1016/0010-2180(94)00136-G ↗
33. Soot inception temperature and the carbonization rate of precursor particles10.1016/S0010-2180(02)00374-7 ↗
34. Mechanisms of suppressing cup-burner flame with water vapor10.1007/s11431-008-0133-6 ↗
35. Droplet vaporization model for spray combustion calculations10.1016/0017-9310(89)90043-4 ↗