journal article·2022-10

Effect of foam air mixing on flame intensification -- comparative experimental study of foam and water sprays extinguishing transformer oil pool fire

Jinping Tu, Dennis Pau, Tianqi Yang, Shuai Nan, Jiaqing Zhang, Fengju Shang, Kaiyuan Li

Fire Safety Journal· Volume 133
Publisher page

Abstract

In this paper, the mechanism of flame intensification during the suppression of transformer oil pool fire is investigated for foam and water sprays. The results show that the extinguishment time is proportional to the discharge height and inversely proportional to the discharge pressure because greater height or lower pressure reduces the amount of suppression agent reaching the fuel bed thus extending extinguishment time. The increase of heat release rate following activation is inversely proportional to the discharge height and directly proportional to the discharge pressure; again, affected by the amount of suppression agent. When the nozzle is above the flame, the foam spray is affected by the entrapped air within, resulting in greater flame intensification, which is 3.5 times compared to water spray. For radiation, when the nozzle is above the flame, the heat flux increase is inversely proportional to the discharge pressure, which differs from the relationship for heat release rate increase. This difference is due to the shielding effect of the blanketing spray. For predict the heat release rate increase, an empirical model is developed, and an air mixing coefficient, τ, is introduced for foam spray to account for a 20%–35% increase in the heat release rate.
Source: expertdata · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Combustion and Detonation Processes · Combustion and flame dynamics

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (43)

Show source-provided references
1. Full-scale experimental and numerical analysis of water mist system for sheltered fire sources in wind generator compartment10.1016/j.psep.2015.05.011 ↗
2. Gasoline fire extinguishing by 0.7 MPa water mist with multicomponent additives driven by CO210.1016/j.psep.2019.07.002 ↗
3. Experimental investigation of the performance of an effective self-suctioning water mist generator for controlling underground coal fires10.1016/j.psep.2019.03.038 ↗
4. Experimental investigation on spray characteristics of twin-fluid nozzle for water mist and its heptane pool fire extinguishing performance10.1016/j.psep.2021.01.037 ↗
5. Characteristics of water mist for fire suppression in enclosures
6. A closer look at the fire extinguishing properties of water mist10.3801/IAFSS.FSS.4-47 ↗
7. Atreya · 1994
8. Characterization of a simplex water mist nozzle and its performance in extinguishing liquid pool fire10.1016/j.expthermflusci.2018.01.015 ↗
9. Jackson · Boilover. Industrial Fire World · 2000 · 15 · 26
10. Study on flame expansion phenomenon in pool fire extinguished by water mist10.1016/j.proeng.2011.04.695 ↗
11. Lu · 2006
12. Experimental and numerical study of water spray system for a fire event in a confined and mechanically ventilated compartment10.1002/fam.2719 ↗
13. On the fire intensification of pool fire with water mist10.1016/j.proeng.2013.08.153 ↗
14. Interaction of water mists with a diffusion flame in a confined space10.1016/S0379-7112(99)00020-X ↗
15. On the interaction of a liquid droplet with a pool of hot cooking oil10.1016/S0379-7112(03)00048-1 ↗
16. Collision dynamics of a single water droplet impinging on a high-temperature pool of oil10.1007/s00707-017-2071-5 ↗
17. Simulated research into the dynamic process of water-drop impact on the hot ghee surface
18. Experimental study on the vapor explosion process of a water drop impact upon hot molten-ghee surface10.1016/j.jlp.2017.03.013 ↗
19. Single droplet with or without additives impacting on high-temperature burning liquid pool10.1016/j.ijheatmasstransfer.2019.04.145 ↗
20. Experimental study of flame expansion induced by water droplet impact on the burning cooking oil10.1016/j.fuel.2020.117497 ↗
21. Experimental study on effect of foam stabilizers on aqueous film-forming foam10.1007/s10694-017-0681-z ↗
22. Experimental comparison of Oxygen Consumption Calorimetry and Sensible Enthalpy Rise Approach for determining the heat release rate of large-scale lithium-ion battery fires10.1016/j.firesaf.2021.103447 ↗
23. Heat release rate calculation in oxygen consumption calorimetry10.1016/j.applthermaleng.2010.09.010 ↗
24. Pyrolysis kinetics and determination of organic components and N-alkanes yields of Karamay transformer oil using TG, FTIR and Py-GC/MS analyses10.1016/j.fuel.2021.121691 ↗
25. Extensive thermogravimetric and thermo-kinetic study of waste motor oil based on iso-conversional methods10.1016/j.enconman.2020.113194 ↗
26. Performance requirements and test methods for sprinkler heads for automatic sprinkler systems. National Standards the People's Republic of China of GB515.3-2003, 2003(in Chinese).
27. Merging dynamics of dual parallel linear diffusion flames10.1016/j.firesaf.2021.103490 ↗
28. Numerical analysis of the effect of horizontal distance between a water mist nozzle and ignition source on reduction in heat release rate10.1016/j.anucene.2020.107560 ↗
29. Fire-extinguishing performance and mechanism of aqueous film-forming foam in diesel pool fire10.1016/j.csite.2019.100578 ↗
30. Experimental study on the extinguishing efficiency of compressed air foam sprinkler system on oil pool fire10.1016/j.proeng.2017.12.142 ↗
31. A theoretical and experimental study of extinguishing compressed air foam on an n-heptane storage tank fire with variable fuel thickness10.1016/j.psep.2020.03.011 ↗
32. Large hydrocarbon fuel pool fires: physical characteristics and thermal emission variations with height10.1016/j.jhazmat.2006.08.057 ↗
33. Modelling large LNG pool fires on water10.1016/j.jlp.2018.08.008 ↗
34. Experimental investigation of spray formation as affected by sprinkler geometry10.1016/j.firesaf.2011.01.003 ↗
35. Estimate of flame radiance via a single location measurement in liquid pool fires10.1016/0010-2180(91)90102-H ↗
36. Statistical aggregation of heat flux measurements for Bayesian inference of a burner fire's radiative fraction10.1016/j.firesaf.2022.103559 ↗
37. Total emission of soot and thermal radiation by free turbulent diffusion flames10.1016/0010-2180(82)90080-3 ↗
38. Hurley · 2016
39. Impacts of longitudinal air velocity and fuel flow rate on flame radiative fraction in tunnel10.1016/j.scs.2020.102336 ↗
40. McGrattan · 2004
41. Experimental research on the combustion characteristics of transformer oil jet fires in oil-filled equipment under heat10.1021/acsomega.1c04551 ↗
42. Experimental study of water sprays for the attenuation of fire thermal radiation10.1115/1.1371921 ↗