First developments of a new test to evaluate the fire behavior of photovoltaic modules on roofs
Source abstract
Abstract
Abstract A new test for photovoltaic (PV) modules exposed to an external fire source on roofs is proposed, and first results are presented. This is a simplification of the standards commonly in use for testing PV modules as roofing parts, roofing components or building components. Most of the tests required different fire scenarios and the use of burning brands such as wood cribs. In our study we proposed replacing wooden burning brands with a propane burner, the output of which is close to the one that can be observed in the burning of wooden cribs 500 g and 2 kg in size. The fire behavior was assessed by measuring smoke evolution, burning drips, flaming debris, and the time to burn-through of monocrystalline, polycrystalline and amorphous silicon panels. Two different configurations of the burner were tested, with the fire source on the top of the module or under the tilted module, respectively. The fire behavior of the modules was dependent on the burner output (16 to 46 kW), but also on the construction type of the panel (glass/glass or glass/plastic sheet) and on the position of the fire source (top or bottom). These preliminary tests for further development of the procedure yielded encouraging results for the evaluation of PV panels on roofs.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Fire effects on ecosystems · Lightning and Electromagnetic Phenomena
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (13)
Show source-provided references
1. Das Jahr des Tigers, Photon-das Solarstrom Magazin, April 2011, pp. 38–71.
2. B. Messerschmidt Fire testing of low slope roof assemblies an international review, in: Proceedings of the 13th International Conference and Exhibition Fire and Materials 2013, San Francisco, USA, 28–30 January 2013, pp. 35–46.
3. DFV Deutsche Feuerwehr Verband, Handlungsempfehlungen Photovoltaikanlagen. September 2010.
4. German Institute for Civil Engineering DiBt. Building inspection requirements for solar systems, in: Proceedings of the DIBt Symposium, Berlin, Germany, 22 October 2012.
5. DIN 4102-7. Fire behavior of building materials and elements. -Roofing; requirements and testing. July 1998.
6. DIN 4102-1. Fire behavior of building materials and elements. -Classification of building materials- requirements and testing. July 1998.
7. DIN EN 13501-1. Fire classification of construction products and building elements. -Part 1: Classification using data from reaction to fire tests; German version. 2009.
8. ISO 11925-2. Reaction to fire tests for building products. -Ignitability when subjected to direct impingement of flame. July 2012.
9. CEN/TS 1187. Test methods for external fire exposures to roofs. -Test 1- Method with burning brands. 2012.
10. IEC 61730-2. Photovoltaic (PV) module safety qualifications. -Requirements for testing. 2004.
11. UL 790. Underwriters Laboratories Inc., Standard test methods for fire tests of roof coverings. USA, 2004.
12. S. Krüger, B. Teichmann, Systematical fire tests of PV modules-research on fire resistance, toxicology and burning behavior, in: Proceedings of the 13th International Fire Science & Engineering. (Conference Interflam, Egham, UK, 24–26 July). 2013, pp.105–113.
13. Recent advances in the use of zinc borates in flame retardancy of EVA10.1016/S0141-3910(98)00130-X ↗