An experimental study to assess the feasibility of a three stage thermal conductivity model for intumescent coatings in large space fires
Source abstract
Abstract
This paper presents the results of an experimental study to investigate the performance of intumescent coatings exposed to large space fires, focusing in particular on the feasibility of a three stage constant effective thermal conductivity model. A total of 54 steel plates protected by intumescent coatings with different thicknesses were tested under the ISO 834 standard fire and three large space fire temperature-time curves. . It was found that the performance of intumescent coatings could be divided into three different stages: melting, expanding and fully expanded, when the steel temperatures were in the ranges of 100℃-300℃, 300℃-400℃ and higher than 400ºC respectively. This paper assesses the feasibility of representing the temperature dependent thermal conductivity of intumescent coatings in large space fires by using three constant effective thermal conductivities corresponding to the three stages. The results of this research indicate that the constant effective thermal conductivities of intumescent coatings for the fully expanded stage under large space fire are similar to those under the ISO 834 standard fire condition. However, different fires affect the constant effective thermal conductivities of intumescent coatings for the melting stage, which increase with the heating rate of fire. The constant thermal conductivities of intumescent coatings for the expanding stage remain relatively stable under different fires, at about half of the values for the expanded stage. The applicability of the three-stage constant effective thermal conductivity model for large space fires has been checked by comparison between the calculated steel temperatures using the three stage constant thermal conductivity model and the test results. The proposed three-stage thermal conductivity model allows the fire test results under the ISO 834 standard fire condition to be adapted to large space fires, and simplifies the calculation procedure for temperatures of intumescent coating protected steel in large space fires.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Flame retardant materials and properties · Combustion and Detonation Processes
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (22)
Show source-provided references
1. Li · 2006
2. Wang · 2013
3. Taylor · 1992
4. ISO 834-1: 1999 · 1999
5. Drysdale · 1999
6. Intumescent fire protective coating: toward a better understanding of their mechanism of action10.1016/j.tca.2006.07.008 ↗
7. Characterization of the performance of an intumescent fire protective coating10.1016/j.surfcoat.2006.01.026 ↗
8. Intumescent coatings: a review on recent progress10.1007/s11998-016-9815-3 ↗
9. Global modelling of fire protection performance of intumescent coating under different cone calorimeter heating conditions10.1016/j.firesaf.2012.02.004 ↗
10. Yuan · 2009
11. EN 13381-8 · 2013
12. Assess the fire resistance of intumescent coatings by equivalent constant thermal resistance10.1007/s10694-011-0243-8 ↗
13. GB 51249-2017 · 2017
14. Predicting intumescent coating protected steel temperature in fire using constant thermal conductivity10.1016/j.tws.2015.03.008 ↗
15. Constant effective thermal conductivity of intumescent coatings: analysis of experimental results10.1177/0734904117693857 ↗
16. Experimental study of the influence of topcoat on insulation performance of intumescent coatings for steel structures10.1016/j.firesaf.2018.08.006 ↗
17. Han · 2017
18. L. Wang, Y. Dong, C. Zhang et al. Experimental study of heat transfer in intumescent coatings exposed to non-standard furnace curves, Fire Technol.., 51(3), 627-643..10.1007/s10694-015-0460-7 ↗
19. Novel testing to study the performance of intumescent coatings under non-standard heating regimes
20. Experimental study of the performance of intumescent coatings exposed to standard and non-standard fire conditions10.1016/j.firesaf.2017.10.004 ↗
21. CECS 200:2006 · 2006
22. The modeling of heat transfer across intumescent polymer coatings10.1177/0734904109346396 ↗