In this study, experiments were conducted on a full-scale cable interlayer experimental platform to investigate the evolution of early fires (smoldering and initial fires) in cable interlayers. Additionally, the temperature field of the fire spread and CO gas propagation characteristics were studied. The effectiveness of point-type temperature detectors, point-type smoke detectors, cable-type temperature detectors, and suction-type smoke detectors with different response time thresholds were analyzed from experiments and numerical simulation. The results revealed that the temperature fields of early fires exponentially decay in long and narrow spaces. Further, although the average propagation velocity of CO in a smoldering fire remains almost constant with increasing distance from the fire source, it decreases gradually in an initial fire. The cable-type temperature detector that remains in direct contact with the cable exhibited the shortest response time, with the non-contact detectors, including the point-type smoke detector and the suction-type smoke detector, exhibiting relatively long response times. In particular, the point-type temperature detector failed to generate a response at all in this case. Finally, the response times of fire detectors with high alarm thresholds were observed to be 10–20% higher than those of fire detectors with low thresholds.
Source: expertdata · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Evacuation and Crowd Dynamics · Fire effects on ecosystems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (31)

Show source-provided references
1. Experiment and numerical simulation of cable trench fire detection10.1016/j.csite.2021.101338 ↗
2. Cable tunnel fire experiments based on linear temperature sensing fire detectors10.3788/OPE.20132109.2225 ↗
3. Cable tunnel fire experiment study based on linear optical fiber fire detectors
4. Detection and prediction of internal-caused fire in tunnel cable by an equivalent transient thermal circuit model10.1155/2021/5618575 ↗
5. Improved assessment of fire spread over horizontal cable trays supported by video fire analysis10.1007/s10694-018-0788-x ↗
6. Fire extinguishing system and temperature profile in confined space10.18494/SAM.2020.2852 ↗
7. Downes · 2004 · vol. 2 · 1804
8. Calibrating single-ended fiber-optic Raman spectra distributed temperature sensing data10.3390/s111110859 ↗
9. External heating of electrical cables and auto-ignition investigation10.1016/j.jhazmat.2016.09.042 ↗
10. Thermal degradation of PVC cable insulation studied by simultaneous TG-FTIR and TG-EGA methods
11. Study on new electrical fire monitoring technology for low-voltage distribution cabinet
12. Detection of semi-volatile plasticizers as a signature of early electrical fire10.3389/fmats.2019.00250 ↗
13. Identification and gas sensor testing of volatile signature gas for early detection of PVC cable fires
14. Experiments on development, spreading and detection of cable fires10.1016/0029-5493(91)90338-I ↗
15. Performance of dual photoelectric/ionization smoke alarms in full-scale fire tests
16. 2006
17. Fire behaviour of electrical cables in cone calorimeter: influence of cables structure and layout10.1016/j.firesaf.2018.05.001 ↗
18. 2018
19. Optimization of emergency ventilation mode for a train on fire stopping beside platform of a metro station10.1007/s12273-013-0143-6 ↗
20. Experimental study on smoke temperature distribution under different power conditions in utility tunnel10.1016/j.csite.2018.03.002 ↗
21. Study on temperature distribution and CO diffusion induced by cable fire in L-shaped utility tunnel10.1016/j.scs.2020.102407 ↗
22. Experimental study on flammability and flame spread characteristics of polyvinyl chloride (PVC) cable10.3390/polym12122789 ↗
23. Modeling fire-induced smoke spread and carbon monoxide transportation in a long channel: fire Dynamics Simulator comparisons with measured data10.1016/j.jhazmat.2006.08.075 ↗
24. Numerical study of a fire-driven flow in a narrow cavity10.1016/j.firesaf.2019.102834 ↗
25. Karlsson · 2008
26. Quintiere · 2006
27. National fire alarm and signaling Code
28. Particulate entry lag in spot-type smoke detectors10.3801/IAFSS.FSS.6-779 ↗
29. 2014
30. 2005