Experimental and numerical study on the interaction of a water mist spray with a turbulent buoyant flame
Source abstract
Abstract
Abstract This paper presents a detailed experimental and numerical study on the interaction, at a reduced scale, between a turbulent buoyant propane flame of about 15.5 kW and a water mist spray with a flow rate of 0.43 L/min from a nozzle positioned at 1 m above the burner. The water spray has been characterized experimentally without a fire, by measuring the water mass flux and droplet size distributions at the level of the burner surface. The whole assembly was installed under a hood and the following three parameters were measured: (1) the chemical heat release rate (HRR) (using the oxygen consumption method), (2) the rise in gas temperature at the top, and (3) the radiative heat flux at 0.72 m from the axis of the burner and at a height of 0.05 m. Reductions of about 40% and 30% were recorded for, respectively, the gas temperature (in the hood) and the radiative heat flux, while the chemical HRR did not change. Computational Fluid Dynamics (CFD) simulations with the Fire Dynamics Simulator (FDS, version 6.7.0) predicted relatively well the gas temperature, without a reduction in the HRR, but, in contrast to the experiments, the radiative heat flux did not change.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Combustion and Detonation Processes · Combustion and flame dynamics
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (18)
Show source-provided references
1. Experimental and numerical study of high-pressure water-mist nozzle sprays10.1016/j.firesaf.2016.01.015 ↗
2. Spray characterization measurements of a pendent fire sprinkler10.1016/j.firesaf.2012.07.007 ↗
3. Characterization of interactions between hot air plumes and water sprays for sprinkler protection10.1016/j.proci.2014.05.078 ↗
4. Performance evaluation of water mist fire suppression: a clean and sustainable fire-fighting technique in mechanically-ventilated place10.1016/j.jclepro.2018.10.315 ↗
5. Suppression effectiveness of water-mist sprays on accelerated wood-cribfires10.1016/j.firesaf.2014.08.012 ↗
6. Numerical modelling of the interaction between water sprays and hot air jets–part i: gas phase large eddy simulations10.1016/j.firesaf.2017.11.005 ↗
7. Numerical modelling of the interaction between water sprays and hot air jets–part ii: two-phase flow simulations10.1016/j.firesaf.2018.01.006 ↗
8. Numerical analysis on the rapid fire suppression using a water mist nozzle in a fire compartment with a door opening10.1016/j.net.2018.10.026 ↗
9. Kevin McGrattan, Simo Hostikka, Randall McDermott, Jason Floyd, Marcos Vanella, Fire Dynamics Simulator User's Guide, NIST Special Publication 1019 sixth ed.
10. Fire cooling performance by water sprays using medium and small-scale model experiments with scaling relaxation10.1016/j.firesaf.2020.102965 ↗
11. Modeling of bare and aspirated thermocouples in compartment fires10.1016/S0379-7112(99)00034-X ↗
12. Measurement of drop size in horizontal annular flow with the immersion method10.1007/s00348-002-0425-8 ↗
13. Droplet size measurement of liquid atomization by the immersion liquid method (droplet coalescence and solution into the immersion liquid)
14. Parker · 1982
15. 2016
16. McCaffrey · 1979
17. Measurements of water density and droplet size distributions of selected ESFR sprinklers10.1177/104239159400600202 ↗
18. Kevin McGrattan, Simo Hostikka, Randall McDermott, Jason Floyd, Marcos Vanella, Fire Dynamics Simulator User's Guide, NIST Special Publication 1019 Sixth Edition, 260 p.