Abstract

A computational model predicting extent of smoke clouds from possible clean room fires has been developed using CO2 concentration as a marker for smoke concentration, which is believed to be more rigorous than the conventional approach relying on temperature profiles. The computational results are compared with results of reduced scale clean room fire tests and are found to be favorable enough to be used in field applications. The numerical model is employed for simulations of clean room fires with a typical full-scale geometry. The impact of air circulation rate, fire size, and fire location on the extent of CO2 clouds, which could be converted to that of smoke clouds, has been analyzed. Sprinkler actuation and smoke detector locations for fast response with respect to different operating conditions are also discussed. Overall, it has been illustrated that numerical simulations can be adopted as a very useful tool in investigating and customizing optimal set of design parameters at a new facility or estimating a scale of contamination at an existing facility against potential clean room fires.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Evacuation and Crowd Dynamics · Combustion and Detonation Processes

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (10)

Show source-provided references
1. Heskestad G. Escape potential from apartments protected by fire detectors in high-rise buildings. Final Technical Report, FMRC Serial No: 21017, Factory Mutual Research Corporation, Norwood, MA, Contract no. H-2034R, US Department of Housing and Urban Development, NTIS: PB 234014-AS, June, 1974.
2. Measurements of the characteristic lengths of smoke detectors10.1007/BF01857936 ↗
3. Heskestad G, Lutton JC. Novel smoke/flume control for clean rooms. FMRC Technical Report, J. I. 0B0J1. RU, Factory Mutual Research Corporation, Norwood, Massachusetts, 1997.
4. Launder · 1972
5. Numerical simulation of thermal plumes10.1016/0379-7112(93)90029-P ↗
6. A turbulence model for buoyant flows and its application to vertical buoyant jets
7. Nam S. Documentation for REFLEQS Software at FMRC. FMRC Technical Report, J. I. 0R0J2.RA(5), Factory Mutual Research Corporation, Norwood, MA, 1996.
8. Tewarson A. Generation of heat and chemical compounds in fires. The SFPE handbook of fire protection engineers, 2nd ed. Quincy, MA: National Fire Protection Association Press, 1995. [Chapter 3–4],
9. Tewarson · 1995
10. Characteristic properties of fire plume in an enclosure with downward air flow