journal article·2015-11

A performance based approach to defining and calculating adequate firefighting water using s.8.5 of the design guide BS PD 7974:5:2014 (fire service intervention)

Paul Grimwood, Iain A Sanderson

Publisher page

Abstract

The determination of firefighting water requirements in large, tall and complex buildings in the UK has largely been based on data retrieved from studies into full-scale test fires, combined with some real fire research undertaken by the Fire Research Station (FRS) from 1955–1970. This scientific research effectively formed the basis for the design and configuration of rising fire mains (stand-pipes) in tall buildings, as well as water storage provisions for town centre and infrastructure planning. The resulting guidance is also applied to individually isolated buildings that are distanced from the nearest available water supply. However, it is suggested the UK has since fallen behind many international standards and codes, where firefighting water provisions are more reflective of modern building design as movable fire loads, compartment dimensions and window (ventilation) sizes have increased over the years. There have been recent calls in both the UK and USA for the development of a performance based method of calculating firefighting water requirements for design purposes, based on the quantity of water actually being used effectively by firefighters. The recent publication of BS PD 7974:5:2014 (7974) meets this need in calculating ‘adequate’ and effective firefighting water (s.8.5). The research by Glasgow Caledonian University (GCU) provides a framework upon which the ‘7974’ water strategy evolved and is based on an analysis of 5401 building fires that occurred in the UK from 2009 to 2012, where active firefighting was undertaken across a broad range of occupancies. When used in design, any recommended deviations from the prescriptive codes may achieve some cost/benefit advantages, whilst at the same time providing an improved firefighting water flow density (L/min/m2). It is also worth noting that UK prescriptive building codes do not differentiate between the volume of firefighting water storage required for residential or commercial buildings. Furthermore, reductions in compartment size and fire load, or enhancements to passive/active fire protection, may mean even less storage water is required when using the 7974 strategy compared to current code compliance. The GCU research clearly established that the severity of building fires is dependent on the size of compartment in which the fire originates; the containment of fire spread through the provisions of adequate passive or active fire protection; the fire load density and the potential for a fire to reach a fuel controlled burning regime at peak heat release for the compartment at Qmax. It is further demonstrated that the quantity of firefighting water that may be deemed as ‘adequate’ can be presented on a gradient ( Fig. 13), ranging from the lesser amount (L/min) required in residential buildings (low-flow), upwards through offices or commercial mixed use buildings (mid-flow), to industrial and storage facilities (high-flow). This finding is not reflected in current codes. In using the ‘7974’ methodology to calculate adequate firefighting water, simple equations are utilised in this paper for both sprinkler protected and non-sprinklered occupancies. The method can be also be used where either dry or wet rising fire mains (standpipes) are required. In referring to past fire case histories it is then demonstrated that fires can travel across large floor plates, with great speed. A spread rate of >20 m2/min may see a fire develop with such velocity and power that any fire service intervention can become compromised from the outset, unless adequate firefighting water provisions are available and effective fire protection measures are in place.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Evacuation and Crowd Dynamics · Injury Epidemiology and Prevention

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (28)

Show source-provided references
1. Fire and Rescue Services Act. 〈http://www.legislation.gov.uk/ukpga/2004/21/contents〉, 2004
2. Fire Hydrants and Firefighting Supplies, UK Water Industry Research Limited, 2010
3. Evaluation of Fire Flow Methodologies, Hughes Associates, The Fire Protection Research Foundation, NFPA, January 2014
4. National Guidance Document on the Provision of Water for Firefighting, LGA/Water UK, 2007
5. Building Regulations1991 England & Wales (Fire Safety), Approved Document B 2000 Edition, DETR UK
6. British Standards Institution (BSI): BS PD 7974:5:2014; The application of fire safety engineering principles to the design of buildings, Fire and rescue service intervention (Sub-system 5), Figure A1
7. S. Sardqvist, Real Fire Data – Fires in Non-residential Premises in London 1994–1997, Lund University Sweden Report 7003, 1998
8. National Fire Protection Association, NFPA 14:2013, Standard for the installation of standpipe and hose systems
9. 〈https://www.dropbox.com/sh/4a799hfyacevfgz/AAC1yJUeaSXUGa-ymLju8rHaa?dl=0〉
10. Building Regulations 2000 England & Wales (Fire Safety), Approved Document B 2006 Edition, DCLG UK (App: ‘D’)
11. Travelling fires for structural design10.1016/j.firesaf.2012.06.003 ↗
12. Buchanan · 2001
13. R.L. Alpert, The Fire Induced Ceiling Jet Re-visited, 〈http://www.see.ed.ac.uk/FIRESEAT/files11/FS11-Proc-Alpert.pdf〉 2014 (retrieved link on 09.10.14)
14. 〈http://www.mace.manchester.ac.uk/project/research/structures/strucfire/CaseStudy/HistoricFires/BuildingFires/interstateBank.htm〉 retrieved link on 15.10.14
15. Barnett · 2004
16. Use of water in the extinction of large fires
17. I. Fletcher, Tall concrete buildings subjected to vertically moving fires p46 (Ph.D. thesis), University of Edinburgh, 2009
18. P. Grimwood, A study of 5401 UK building fires 2009–2012 comparing firefighting water deployments against resulting building fire damage (Ph.D. thesis), Glasgow Caledonian University, School of Engineering and the Built Environment, 2015
19. Jorge Capote, Daniel Alvear, Mariano Lázaro, Jorge Crespo. Assessment of the thermal response of high-rise buildings under natural fires using CFD and FEM analysis, Paper Ref: S2001_P0302 3rd International Conference on Integrity Reliability and Failure, Porto/Portugal, 20–24 July, 2009
20. Grimwood · 1992 · 7 · 266
21. Grimwood · 2008 · 305
22. Grimwood · 1992 · 235
23. British Standards Institute, BS 9990, 2015
24. S. Särdqvist, An Engineering Approach to Firefighting Tactics, Lund University Sweden Report 1014, 1996
25. D.J. Rasbash, The extinction of fire with plain water: a review, Fire Safety Science, in: Proceedings of the First International Symposium, Springer-Verlag Berlin, 1986, pp. 1145–116310.3801/IAFSS.FSS.1-1145 ↗
26. On the extinguishing effect of various extinguishing agents and extinguishing methods with different fuels10.1016/0379-7112(84)90037-7 ↗
27. The County/Metro research into fire-fighting suppressive capacity and the impact on building fire damage at >5000 UK building fires, 2009–201210.1016/j.firesaf.2014.11.027 ↗
28. 〈https://www.dropbox.com/sh/4a799hfyacevfgz/AAC1yJUeaSXUGa-ymLju8rHaa?dl=0〉