Inert gas discharge time effects on full and reduced scale wood crib extinguishing experiments
Source abstract
Abstract
The 2012 edition of NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems, was revised to allow a maximum 2-min discharge duration for systems that protect class A fire hazards with inert gases. With this change, UL 2127 and FM 5600 also began testing and certifying systems over both 60- and 120-s discharge durations. This study analyzes the effect of the different discharge times of an inert agent on the extinction of a test article (wood crib) placed within an enclosure. This was done following the UL 2127 procedure, and a modified version of it that involved the use of a reduced-scale experimental setup. The enclosure was scaled based on the oxygen consumption of the wood crib. Observations and measurements included oxygen concentration within the enclosure, near-crib gas velocity and temperature, as well as wood crib mass. These quantities were used to study the extinguishment differences at the two discharge durations and support the validity of a novel ¼ reduced-scale crib and enclosure developed in this study. It was found that varying the discharge time will induce changes in the suppression dynamics, as the flow of agent and entrained air affect the time to reach extinction.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Combustion and Detonation Processes · Fire Detection and Safety Systems
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (24)
Show source-provided references
1. di Nenno · 2016 · 1483
2. Nitrogen as an environmentally friendly suppression agent for aircraft cargo fire safety10.1177/07349041211034456 ↗
3. Numerical assessment for aircraft cargo compartment fire suppression system safety10.1177/07349041211003208 ↗
4. 2011 · 2010
5. Performance evaluation of nitrogen for fire safety application in aircraft10.1016/j.ress.2020.107044 ↗
6. Nitrogen gas as a halon replacement
7. J. Gałaj and T. Drzymała, “Assessment of extinguishing efficiency of hybrid system using water mist and inert gas during class A fires,” Matec-Conf.org., doi: 10.1051/matecconf/201824700013.10.1051/matecconf/201824700013 ↗
8. Evaluation of an oxygen reduction system (ORS) in large-scale fire tests10.1016/j.firesaf.2019.03.013 ↗
9. Flame extinguishing in the cup-burner by inert gases10.1016/j.firesaf.2005.05.008 ↗
10. 2018
11. Organization · 2006
12. Approvals · 2021
13. Effect of inert gas discharge time on wood crib fires in reduced-scale and full-scale experiments
14. Free burning fires10.1016/0379-7112(86)90051-2 ↗
15. Experiments on the burning of cross piles of wood
16. Scale modeling of quasi-steady wood crib fires in enclosures10.1016/j.firesaf.2004.12.002 ↗
17. Modeling of enclosure fires10.1016/S0082-0784(73)80092-X ↗
18. A theoretical and experimental study of nonpropagating free-burning fires10.1016/S0082-0784(71)80097-8 ↗
19. Burning rates of wood cribs with implications for wildland fires10.1007/s10694-015-0543-5 ↗
20. Shaddix
21. A methodology for estimation of local heat fluxes in steady laminar boundary layer diffusion flames10.1016/j.combustflame.2015.01.019 ↗
22. Drysdale · 2011
23. McAllister · 2016 · vol. 52
24. Tapscott · 1999 · 265