Rise in structural steel temperatures during ISO 9705 room fires
Source abstract
Abstract
An experimental programme was undertaken to study the temperature rise of protected and unprotected structural steel during a fire within a small enclosure (an ISO 9705 room). The fuel (wood crib) was placed at two locations (front and back) within the ISO room. Each location had two fire scenarios present: the first fire scenario was for recording the temperatures of protected steel members within the enclosure, and the second fire scenario was to measure the temperatures of the directly exposed members. Six steel columns and two steel beams were strategically placed, and their temperatures were measured. Other data recorded were gas temperatures and heat release rates (HRRs). Thermocouples were kept in identical locations during the tests with protected and unprotected steel members to facilitate direct comparison. Despite the natural variability in fire development in identical situations, data up to ≈20 min were found suitable for direct comparison between protected and unprotected steel members. Comparison of these results with Fire Dynamics Simulator (FDS) version 5.3.1 modelling (with prescribed HRRs) results is presented to show the usefulness of the data collected.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Fire effects on concrete materials · Combustion and Detonation Processes
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (18)
Show source-provided references
1. I.R. Thomas, I.D. Bennetts, P. Dayawansa, D.J. Proe, R.R. Lewins, Fire tests of the 140 William St office building, BHP Research—Melbourne Laboratories Rep. No. BBPR/ENG/R/92/043/SG2C, February 1992.
2. Swinden Technology Centre · 1999
3. Kirby · 1994
4. A. Hamins, K. McGrattan, K. Prasad, A. Maranghides, T. McAllister, Fire safety science, in: Proceedings of the Eighth International Symposium, International Association for Fire Safety Science, 2005, pp. 189–200.10.3801/IAFSS.FSS.8-189 ↗
5. K. McGrattan, S. Hostikka, J. Floyd, Fire Dynamics Simulator (Version 5) User's Guide, NIST Special Publication 1019-5, National Institute of Standards and Technology, U.S. Department of Commerce, Gaithersburg, Maryland, USA, February 2009.
6. International Organization for Standardization · 1993
7. Estimation of rate of heat release by means of oxygen consumption measurements10.1002/fam.810040202 ↗
8. Standards Australia, Steel Structures, Australia Standard AS4100-1998.
9. Buchanan · 2001
10. Effects of radiation on temperature measurement in a fire environment10.1177/073490419701500602 ↗
11. V. Babrauskas, Temperature in flames and fires. 〈http://www.doctorfire.com/flametmp.html〉, 25 February 2006, (retrieved 01 April, 2010).
12. J.S. Al-Menhali, ISO 9705 Room Fire Tests of Protected and Unprotected Structural Steels. Masters Dissertation, Centre for Environmental Safety and Risk Engineering, Victoria University, Australia, 2010.
13. The effect of fuel quantity and location in small enclosure fires10.1177/1042391506064908 ↗
14. Kodur · 2004
15. McGrattan · 2010
16. Holman · 1989
17. K.A.M. Moinuddin, J.D. Li, A new convective heat transfer model for fire dynamics simulator, in: Proceedings of the 13th Asian Congress for Fluid Mechanics, December 17–21, 2010, Dhaka, pp. 819–822.