Assessment of heating and evaporation modelling based on single suspended water droplet experiments
Source abstract
Abstract
The work described in this paper is undertaken with the purpose of providing a detailed assessment of the current modelling capabilities of the effects of fire suppression systems (e.g., sprinklers) in fire-driven flows. Such assessment will allow identifying key modelling issues and, ultimately, improving the reliability of the numerical tools in fire safety design studies. More specifically, we studied herein the heating and evaporation of a single water droplet. This rather 'simple' configuration represents the first step in a tedious and rigorous verification and validation process, as advocated in the MaCFP (Measurement and Computation of Fire Phenomena) working group (see https://iafss.org/macfp/). Such a process starts ideally with single-physics 'unit tests' and then more elaborate benchmark cases and sub-systems, before addressing 'real-life' application tests. In this paper, we are considering the recently published comprehensive and well-documented experimental data of Volkov and Strizhak (Applied Thermal Engineering, 2017) where a single suspended water droplet of initial diameter between 2.6 and 3.4 mm is heated up by a convective hot air flow with a velocity between 3 and 4.5 m/s and a temperature between 100 and 800 degrees C. In the present numerical study, 36 experimental tests have been simulated with the Fire Dynamics Simulator (FDS 6.7.0) as well as with an in-house code. The results show that the droplet lifetime is overpredicted with an overall deviation between 26 and 31%. The deviation in the range 300-800 degrees C is even better, i.e., 5-8%, whilst the cases of 200 and, more so 100 degrees C, showed much stronger deviations. The measured droplet saturation temperatures did not exceed 70 degrees C, even for high air temperatures of around 800 degrees C, whereas the predicted values approached 100 degrees C. A detailed analysis shows that the standard Ranz & Marshall modelling of the non-dimensional Nusselt and Sherwood numbers may not be appropriate in order to obtain a simultaneous good agreement for both the droplet lifetime and temperature. More specifically, the heat-mass transfer analogy (i.e., Nu = Sh) appears to be not always valid.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Fire effects on ecosystems · Evacuation and Crowd Dynamics
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (19)
Show source-provided references
1. Modelling of fuel droplet heating and evaporation: recent results and unsolved problems10.1016/j.fuel.2017.01.048 ↗
2. Evaporation from drops
3. Planer laser-induced fluorescence diagnostics of water droplets heating and evaporation at high-temperature10.1016/j.applthermaleng.2017.08.040 ↗
4. The integral characteristics of the deceleration and entrainment of water droplets by the counter flow of high-temperature combustion products10.1016/j.expthermflusci.2016.01.018 ↗
5. Development and evaluation of two new droplet evaporation schemes for fire dynamics simulations10.1016/j.firesaf.2017.04.036 ↗
6. McGrattan · 2017
7. McGrattan · 2017
8. The evaporation of water droplets. A single droplet drying experiment10.1081/DRT-120029992 ↗
9. Study of water-mist behaviour in hot air induced by a room fire: model development, validation and verification10.1002/fam.2279 ↗
10. Improving the glass-filament method for accurate measurement of drying kinetics of liquid droplets10.1205/026387602317446443 ↗
11. Numerical modeling of radiative heat transfer in water sprays10.1016/j.firesaf.2005.09.003 ↗
12. Transient temperature gradient in a single-component vaporizing droplet10.1016/j.ijheatmasstransfer.2013.05.064 ↗
13. Mass transfer from a drop – I. Experimental study and comparison with existing correlations10.1016/0017-9310(94)90315-8 ↗
14. The evaporation of drops of pure liquids at elevated temperatures: rates of evaporation and wet-bulb temperatures10.1002/aic.690120424 ↗
15. Incropera · 1996
16. Accurate numerical estimation in Lagrangian-Eulerian simulations of dispersed two-phase flows10.1016/j.ijmultiphaseflow.2007.06.002 ↗
17. Sikanen · 2017
18. Quantifying the predictive uncertainty of complex numerical models10.1088/0026-1394/48/3/011 ↗
19. Coefficients for calculating thermodynamic and transport properties of individual species