Air entrainment into balcony spill plumes
Source abstract
Abstract
Abstract New plume formulations have been developed for assessing air entrainment into thermal plumes that spill over a balcony edge into an atrium void. A simple weak rectangular plume treatment is developed to incorporate the effects of entrainment into plume ends. This is shown to be asymptotic to two dimensional, line plume (near the balcony) and three dimensional axisymmetric plume limits (in the far field). In addition a strong curved plume analysis that also includes the influences of the horizontal momentum of the smoke layer at the balcony edge is developed. The results of the analytical formulations have been compared with Harrison’s new comprehensive experimental data [1] and with CFD predictions from the JASMINE CFD model. It is shown that a virtual line source located a distance approximately three layer depths below the balcony edge provides a reasonably good description of mass fluxes for plumes with and without end entrainment. It is concluded that for practical engineering application, a simple rectangular plume treatment describes the transition from two- to three dimensional flow sufficiently well to be a simple option for the inclusion of end effects.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Wind and Air Flow Studies · Fire dynamics and safety research · Aerodynamics and Acoustics in Jet Flows
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (23)
Show source-provided references
1. R. Harrison and M. Spearpoint, Characterisation of balcony spill plume entrainment using physical scale modelling, in: Proceedings of the 9th International Symposium on Fire Safety Science, IAFSS, 2009, pp. 727–73810.3801/IAFSS.FSS.9-727 ↗
2. G. Cox and S. Kumar, Modelling Enclosure Fires Using CFD, 3rd edition, SFPE Handbook, Section 3, Society of Fire Protection Engineers, Bethesda, 2002, pp. 194 3–218 (Chapter 8).
3. S. Miles, S. Kumar & G. Cox, The balcony spill plume—some CFD simulations, in: Proceedings of the 5th International Symposium on Fire Safety Science, IAFSS, 1997, pp. 237–24710.3801/IAFSS.FSS.5-237 ↗
4. BSI 7974, Part 2: Spread of smoke and toxic gases within and beyond the enclosure of origin, 2002.
5. CIBSE Guide Volume E: Fire Engineering, Chartered Institution of Building Services Engineers, London, UK, 1997.
6. NFPA 92B, Standard for Smoke Management Systems in Malls, Atria and Large Spaces, National Fire Protection Association, Quincy, MA, 2005.
7. H.P. Morgan & N.R. Marshall Smoke control measures in covered two-storey shopping mall having balconies as pedestrian walkways, BRE Current Paper 11/79, Garston, BRE, 1979.
8. G.O. Hansell, N.R. Marshall & H.P. Morgan Smoke flow experiments in a model atrium, BRE Occasional Paper OP55, Garston, BRE, 1993.
9. H.P. Morgan & N.R. Marshall Smoke hazards in covered multilevel shopping malls: an experimentally-based theory for smoke production, BRE Current Paper 48/75, Garston, BRE, 1975.
10. H.P. Morgan, B.K. Ghosh, G. Garrad, R. Pamlitscha, J.-C. De Smedt, L.R. Schoonbaert, Design methodologies for smoke and heat exhaust ventilation, BRE Report BR 368, Garston, CRC, 1999.
11. A study of natural convection above a line fire10.1017/S0022112061000573 ↗
12. Measurements of balcony smoke flow10.1016/0379-7112(95)00011-H ↗
13. Entrainment by two-dimensional spill plumes10.1016/S0379-7112(97)00036-2 ↗
14. The spill plume in smoke control design10.1016/S0379-7112(97)00037-4 ↗
15. An experimental study of some line fires10.1016/S0379-7112(96)00047-1 ↗
16. J.G. Quintiere and B.S. Grove, A unified analysis for fire plumes, in: Proceedings of the 27th Symposium (International) on Comb, 1998, pp. 2757–276610.1016/S0082-0784(98)80132-X ↗
17. S. Yokoi, Study on the prevention of fire spread caused by hot upward current, Building Research Report 34, Japanese Ministry of Construction, 1960.
18. Gravitational convection from a buoyancy source10.1111/j.2153-3490.1952.tb01005.x ↗
19. C.J. Chen and W. Rodi, A review of experimental data of vertical turbulent buoyant jets, University of Karlsruhe Report SFB 80/T/69, 1975.
20. On strong two-dimensional plumes10.1016/S0379-7112(99)00050-8 ↗
21. Thomas · Notes on the similarity of turbulent buoyant fire plumes with large density variations, Fire Safety Journal · 2007 · 42 · 43
22. S. Kumar, P.H. Thomas and G. Cox, Novel analytical approach for characterising air entrainment into a balcony spill plume, in: Proceedings of the 9th International Symposium on Fire Safety Science, IAFSS, 2009, pp. 739-750.10.3801/IAFSS.FSS.9-739 ↗
23. G.G. Rooney, Buoyant flows from fires in enclosures, Ph.D. Thesis, Cambridge University, 1997.