Fire tests to evaluate CPVC pipe sprinkler systems without fire resistance barriers
Source abstract
Abstract
Abstract Nine full-scale fire tests were conducted to assess the adequacy of exposed chlorinated poly vinyl chloride (CPVC) pipe and fitting sprinkler systems installed in light hazard occupancies. The tests were conducted in an enclosure using six different types of automatic sprinklers including QREC pendent and sidewall sprinklers, a pendent residential sprinkler, and a sidewall residential sprinkler. Two types of fires, fast growing and slow growing, were used as test fires. The sprinkler in each test was operated with the normal operation pressure until the test fire was almost completely suppressed. Next, to assess the integrity of piping systems after fire exposure, the water pressure was increased to 12.1 bar and maintained for 10 min and then were visually inspected for any leakage while hydrostatic pressure was maintained at 12.1 bar. No leakage was detected in any of the tests. The results of the tests indicate that sprinkler systems based on exposed CPVC pipe and fittings can be safely installed in light hazard occupancies and will provide adequate protection when installed to all the relevant standards.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Fire Detection and Safety Systems · Lightning and Electromagnetic Phenomena
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (7)
Show source-provided references
1. NFPA 13. Standard for the installation of sprinkler systems. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA, USA; 2002.
2. Approval Standard for plastic pipe and fittings for automatic sprinkler systems. Class number 1635, FM Approvals.
3. UL 1821. Thermoplastic sprinkler pipe and fittings for fire protection service. Underwriters Laboratories, Inc., Northbrook, IL; 2001.
4. Nam S. Fire tests to evaluate the integrity of the BlazeMaster® pipe sprinkler systems installed with the Soffi-Steel® covers in light hazard occupancies. Technical report, J.I. 3012913, FM Global Research, Norwood, MA; 2002.
5. Revised Guidelines for the Approval of equivalent fixed gas fire-extinguishing systems, as referred to in SOLAS 74, for machinery spaces and cargo pump-rooms. MSC/Circ. 848, International Maritime Organization, 4 Alpert Embankment, London SE1 75 R; 1998.
6. A new test to evaluate the fire performance of residential sprinklers10.1023/A:1014407200101 ↗
7. BlazeMaster® Fire sprinkler systems, installation and specification manual for architectural engineers and fire sprinkler contractors. Noveon Inc., 9911 Brecksville Road, Cleveland, OH.