The maximum ceiling height of the FM Global laboratory is 18.3 m. Therefore, fire protection solutions for warehouses with taller ceilings cannot be directly validated through full-scale testing. This work develops a methodology to obtain the key processes of fire growth, spray-plume interaction, and fire suppression response for an 18.9 m high roll-paper storage under a 24.4 m tall ceiling. The proposed methodology uses a heptane burner assembly at the base of the commodity array to match the fire heat release and growth rate to that of a taller storage exceeding lab capability. The burner assembly included six heptane burners and two air ducts. A series of experiments was conducted to characterize the burner design, model the fire growth in the free-burn stage, and validate controlled and uncontrolled fires in terms of the number of activated sprinklers. A final large-scale fire test used a 12.8 m high storage of Kraft paper with the burner assembly under an 18.3 m tall ceiling to validate protection recommendations for Kraft paper stored 18.9 m high under a 24.4 m tall ceiling. The test demonstrated full suppression using K360 (K-factor, lpm/bar1/2), fast response, pendent sprinklers with a temperature rating of 74 °C, supplied with a water pressure of 8.3 bar.
Source: expertdata · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Flame retardant materials and properties · Fire Detection and Safety Systems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (11)

Show source-provided references
1. Xin · 2007 · 532
2. 2018
3. Standard for the Installation of Sprinkler System · 2022 · 13
4. Zeng · 2015 · 285
5. An experimental study of fire growth and suppression of roll paper at small scales10.1016/j.firesaf.2017.03.043 ↗
6. Zhou · 2018 · 727
7. Ren · 2015
8. Ren · 2016
9. Meredith · 2019 · 65
10. Scaling the interaction of water sprays and flames10.1016/S0379-7112(02)00012-7 ↗