Operational uptime and other measures of performance of an open car park in fire
Source abstract
Abstract
192 coupled wind and fire CFD simulations were performed using ANSYS Fluent to study the wind and fire interaction in an open car park. The natural ventilation was insufficient for removal of smoke and heat for the majority of investigated fires. Blockage effect was observed for wind directions parallel to the open walls, which resulted in reduced smoke removal and higher smoke temperatures. With known probabilities of all the investigated wind speed and directions, we have estimated the percentage of time in which fire outcomes are acceptable. This value was coined as the car park operational uptime, and was 84.9 %–92.8 % in relation to the fire with HRR = 1.4 MW; 36.5 %–56.1 % at 4.0 MW; 34.1 %–54.4 % at 6.0 MW and 12.13–25.5 % at 8.8 MW. In 6.22 % of wind cases, the velocity inside the car park exceeded 3.0 m/s, which could potentially contribute to the growth of the fire. Limitations of the study include the assumed wind probability distribution relevant to the Warsaw region, the single location of the fire used in the assessment and the implicit modelling of topography and architecture through an introduced wind profile and terrain roughness model. • Qualitative method of natural smoke control assessment of operational uptime is proposed. • Operational uptime of natural smoke control ranged from 84.9 % to 92.8 % for 1.40 MW design fire. • Operational uptime of natural smoke control ranged from 12.1 % to 25.5 % for 8.80 MW design fire. • Wind perpendicular to open facades yielded the best results. • Wind parallel to open facades caused smoke entrapment in the car park and the worst outcomes.
Source: openalex_inverted_index · Quality: baseline
Research context
OpenAlex topics: Fire dynamics and safety research · Wind and Air Flow Studies · Evacuation and Crowd Dynamics
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (32)
Show source-provided references
1. 2018
2. Storesund · 2020
3. Defining a velocity criterion for stagnant air in buildings
4. Wind and fire coupled modelling—Part II: good practice guidelines10.1007/s10694-018-0749-4 ↗
5. CFD simulation of cross-ventilation flow for different isolated building configurations: Validation with wind tunnel measurements and analysis of physical and numerical diffusion effects10.1016/j.jweia.2012.02.005 ↗
6. A transient transport model for gaseous pollutants in naturally-ventilated partitioned buildings10.1007/s12273-017-0390-z ↗
7. Chained analysis of wind tunnel test and CFD on cross ventilation of large-scale market building10.1016/S0167-6105(97)00101-3 ↗
8. Wind tunnel investigations of sidewall opening effects on indoor airflows of a cross-ventilated dairy building10.1016/j.enbuild.2018.07.026 ↗
9. Natural ventilation design for underground parking garages
10. Experimental study and model predictions on helium release in an enclosure with single or multiple vents10.1016/j.ijhydene.2022.09.030 ↗
11. The Use of Impulse ventilation to control pollution in underground car parks
12. Smoke control in case of fire in a large car park: full-scale experiments
13. On ventilation design for underground car parks10.1016/0886-7798(95)00010-V ↗
14. Wind influence on air flow inside road tunnels
15. The influence of the Arrangement of passenger cars in indoor car parks on CFD calculations
16. Sun · 2020
17. Prediction of time to ignition in multiple vehicle fire spread experiments10.1002/fam.2458 ↗
18. Fire smoke dispersion inside and outside of a warehouse building in moderate and strong wind conditions10.1016/j.firesaf.2023.103760 ↗
19. 2014
20. Computational Fluid Dynamics for urban physics: Importance, scales, possibilities, limitations and ten tips and tricks towards accurate and reliable simulations10.1016/j.buildenv.2015.02.015 ↗
21. Best practice guideline for the CFD simulation of flows in the urban environment
22. On the effect of wind direction and urban surroundings on natural ventilation of a large semi-enclosed stadium10.1016/j.compfluid.2010.02.004 ↗
23. A Comprehensive modelling approach for the Neutral atmospheric boundary layer: Consistent Inflow conditions, wall function and turbulence model10.1007/s10546-011-9621-5 ↗
24. CFD simulation of the atmospheric boundary layer: wall function problems10.1016/j.atmosenv.2006.08.019 ↗
25. Effectiveness of forced ventilation in closed car parks
26. Miechówka · 2023
27. 2005
28. 2010
29. Experimental and numerical evaluation of the influence of the soot yield on the visibility in smoke in CFD analysis10.1016/j.firesaf.2017.03.053 ↗
30. Węgrzyński · 2015
31. 2022
32. Wind effects on smoke motion in buildings10.1016/S0379-7112(00)00017-5 ↗