Sealability Properties of Fluorine-Free Fire-Fighting Foams (FfreeF)
Source abstract
Abstract
This contribution compares the sealability performance of recently developed three synthetic foam formulations (that do not contain fluorosurfactants or fluoropolymers) with that of an aqueous film forming foam (AFFF). We apply the sealability methodology outlined in the Australian Defence Force Specification, DEF(AUST)5706. This methodology specifies a 0.28 m2 small-scale indoor fire pan. The pan is first filled with 10 L of water and then 5 L of AVGAS (aviation gasoline, flash point of −50°C) or heptane (flash point of −4°C) is placed on top of the water. Foams were generated from a pressurised extinguisher with a foam nozzle as described in the standard’s specification, set to create foams with expansion of 4:1. The foam spread across the fuel until the entire fuel surface was covered with foam. At 5 min intervals, a lit taper was introduced into the space above the pan area by passing it twice around the surface of the foam in a circular motion at a height of approximately 15 mm from the surface of the foam. The results demonstrate differences in the sealability performance between AFFF and fluorine-free foams (FfreeF). Under laboratory conditions, with a foam blanket 1–2 cm deep, best-performing FfreeF formulation (RF6) provides about 30% of the durability of an AFFF for protection against evaporation of low-flashpoint flammable liquids. We also note in the results the significant differences among FfreeF with almost no sealability of AVGAS vapours offered by the two other formulations.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Combustion and Detonation Processes · Fluid Dynamics and Heat Transfer
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (12)
Show source-provided references
1. J.A. Pignato Jr., “Evaluation Test for Foam Agent Effectiveness”, Fire Engineering, 1984, pp. 46–48.
2. Cousins C.S., Briggs A.A. (1986) Tests Show Unfoamed Agents Capable of Increasing Fire Potential in Fuels. Fire 78:pp 20–21.
3. D. Stubley and D.J. Mulligan “The Effect of Aqueous Surfactant Films on the Ignitability of Aviation Kerosene”, Fire Technology, 1988, pp. 110–115.10.1007/BF01041336 ↗
4. T.H. Schaefer, B.Z. Dlugogorski, and E.M. Kennedy, “Vapour Suppression of n-Heptane with Fire Fighting Foams Using Laboratory Flux Chamber”, Proceedings of the 7th Asia-Oceania Symposium. Fire Science Technology (in press).
5. DEF(AUST)5706, Foam, Liquid Fire Extinguishing; 3 Percent and 6 Percent Concentrate Specification, Commonwealth of Australia, Australian Defence Standard, 2003.
6. Lide D.R. (2000) CRC Handbook of Chemistry and Physics, 80th Ed., CRC Press, New York, pp. 6–83.
7. DEF(AUST)5215, Gasoline, Aviation, Specification, NATO Code F-18 and F-22 (AVGAS 100/130, 100LL and 115/145), Commonwealth of Australia Australian Defence Standard, 1999.
8. Defence Standard 42-40, issue 2, Foam Liquids, Fire Extinguishing (Concentrates, Foam, Fire Extinguishing), UK Ministry of Defence, 2002.
9. NFPA 412, Standard for Evaluating Aircraft Rescue and Fire-Fighting Foam Equipment, National Fire Protection Association, Quincy, Massachusetts, USA, 1998.
10. US Mil-F-24385F, Fire Extinguishing Agent, Aqueous Film-Forming Foam (AFFF) Liquid Concentrate, for Fresh and Sea Water. Military Specification (Navy), 1992.
11. B.Z. Dlugogorski, S. Phiyanalinmat, and E.M. Kennedy, “Dynamic surface and interfacial tension of AFFF and fluorine-free Class B foam solutions”. Proceedings of the 8th International Symposium on Fire Safety Science. September 2005, Beijing, China, pp. 719–730.10.3801/IAFSS.FSS.8-719 ↗
12. Shah D.O., Djabbarah N.F., Wasan D.T. (1978) A Correlation of Foam Stability with Surface Shear Viscosity and Area per Molecule in Mixed Surfactant Systems. Colloid & Polymer Science 256:pp 1002–1008.10.1007/BF01520987 ↗