Experimental Study on the Burning Behavior of Pool Fires in Rooms with Different Wall Linings
Source abstract
Abstract
An experimental test series, comprising 10 experiments with varying pool sizes, lining materials and amounts of liquid burning, was conducted under free burn and room burn conditions. The thermal feedback from the enclosure (ISO 9705 Room Corner Test facility) enhanced the burning rate of the pools and resulted in a thermal runaway in some of the runs. The onset of the thermal runaway, which can be associated with flashover, varied with all the input parameters. The lining with the lowest thermal inertia lead to the fastest increase in the heat release rate (HRR) in the enclosure and caused flashover in the shortest time. Given the profound difference between the enclosure tests and the free burn tests and also between enclosure tests with different linings, it is recommended to show great caution if free burn tests are to be used in design fire scenarios.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Fire Detection and Safety Systems · Evacuation and Crowd Dynamics
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (24)
Show source-provided references
1. Bwalya A (2008) An overview of design fires for building compartments. Fire Technol 44:167–18410.1007/s10694-007-0031-7 ↗
2. Karlsson B, Quintiere JG (2002) Enclosure fire dynamics. CRC Press, Boca Raton, FL
3. Thomas PH, Bullen ML, Quintiere JG, McCaffrey B (1980) Flashover and instabilities in fire behavior. Combust Flame 38:159–17110.1016/0010-2180(80)90048-6 ↗
4. Babrauskas V (1980) Estimating room flashover potential. Fire Technol 16:94–10310.1007/BF02481843 ↗
5. ISO/TS 16733 (2006) Fires safety engineering—selection of design fire scenarios and design fires. International Organization for Standardization
6. Thomas IR, Moinuddin KAM, Bennets ID (2007) The effect of fuel quantity and location on small enclosure fires. J Fire Protect Eng 17:85–10210.1177/1042391506064908 ↗
7. ISO 9705 (1993) Fire tests—full-scale room test for surface products. International Organization for Standardization
8. Parkes AR (2009) The impact of size and location of pool fires on compartment fire behaviour. Ph.D. Thesis, University of Canterbury, New Zealand
9. Pierce JBM, Moss JB (2007) Smoke production, radiation heat transfer and fire growth in a liquid-fuelled compartment fire. Fire Safety J 42:310–32010.1016/j.firesaf.2006.11.006 ↗
10. Bishop SR, Holborn PG, Beard AN, Drysdale DD (1993) Nonlinear dynamics of flashover in compartment fires. Fires Safety J 21:11–4510.1016/0379-7112(93)90003-9 ↗
11. Graham TL, Makhviladze GM, Roberts JP (1995) On the theory of flashover development. Fire Safety J 25:229–25910.1016/0379-7112(95)00049-6 ↗
12. Beard AN (2003) Dependence of flashover on temperature and aspect ratio of the compartment. J Fire Sci 21:267–28410.1177/0734904103021004002 ↗
13. Graham TL, Makhviladze GM, Roberts JP (1999) The effect of thermal inertia of the walls upon flashover. Fire Safety J 32:35–6010.1016/S0379-7112(98)00022-8 ↗
14. Beard AN (2010) Flashover and boundary properties. Fire Safety J 45:116–121.10.1016/j.firesaf.2009.12.002 ↗
15. Beard AN (2001) Dependence of flashover on assumed value of discharge coefficient. Fire Safety J 36:25–3610.1016/S0379-7112(00)00048-5 ↗
16. Utiskul Y (2007) Theoretical and experimental study on fully-developed compartment fire. Ph.D. Thesis, NIST GCR 07-907
17. Janssens ML (1991) Measuring rate of heat release by oxygen consumption. Fire Technol 27:234–24910.1007/BF01038449 ↗
18. Heskestad G (1983) Virtual origins of fire plumes. Fire Safety J 5:109–11410.1016/0379-7112(83)90003-6 ↗
19. Babrauskas V (1983) Estimating large pool fire burning rates. Fire Technol 19:251–26110.1007/BF02380810 ↗
20. McCaffrey JB, Quintiere JG, Harkleroad MF (1981) Estimating room temperatures and the likelihood of flashover using fire test data correlations. Fire Technol 17:98–11910.1007/BF02479583 ↗
21. Steinhaus T, Welch S, Carvel RO, Torero J (2007) Large-scale pool fires. Therm Sci 11:101–11810.2298/TSCI0702101S ↗
22. EN 13823:2002 Reaction to fire tests for building products—building products excluding floorings exposed to the thermal attack by a single burning item. CEN, European Committee for Standardization
23. Peacock RD, Reneke PA, Bukowski RW, Babrauskas V (1999) Defining flashover for fire hazard calculations. Fire Safety J 32:331–34510.1016/S0379-7112(98)00048-4 ↗
24. DiNenno PE (ed) (2002) The SFPE handbook of fire protection engineering, 3rd edn. National Fire Protection Association, Quincy, MA