Evaluation of Empirical Evidence Against Zone Models for Smoke Detector Activation Prediction
Source abstract
Abstract
A series of experiments were conducted in a large room to generate data to assess the accuracy of computer fire model predictions of detector activation time. A comparison between experimental measurements and zone model predictions of the detector activation in the Consolidated Fire and Smoke Transport model (CFAST) version 7.4.3 were made. The experimental room was 11.0 m by 7.3 m by 3.7 m high with a single opening 2.44 m high and 1.83 m wide centered in a short wall. Two ceiling configurations were examined, a flat ceiling and a flat ceiling with two 0.30 m wide and 0.30 m deep solid beams. The fire source was a gaseous fuel burner fed with different mixtures of propane and propene that produced soot yields ranging from 0.010 gsoot/gfuel to 0.072 gsoot/gfuel and a fuel flow ramp time that ranged from 30 s to 1800 s. The heat release rate profile reached a nominal maximum value of 30 kW. The activations of two different models of photoelectric smoke detectors and a single ionization smoke detector, each with a range of alarm set points and installed at various locations on the ceiling, were recorded. Predictions of the various smoke detector activation times were made in CFAST with the temperature approximation method, and a fixed smoke detector concentration method for photoelectric detector activations. Predictions with the smoke detection method were better than the temperature approximation method over the range of fire scenarios examined. Predictions of smooth ceiling experiments were generally better than the beamed ceiling experiments.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Fire Detection and Safety Systems · Fire effects on ecosystems
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (10)
Show source-provided references
1. Reneke PA, Bruns MD, Gilbert SW, MacLaren C, Peacock, RD, Cleary TG, Butry DT (2019) Toward a process to quantify the hazard of fire protection design alternatives. Technical Note 2041, National Institute of Standards and Technology, Gaithersburg, MD. https://doi.org/10.6028/NIST.TN.204110.6028/NIST.TN.2041 ↗
2. Tam WC, Fu EY, Peacock R et al (2020) Generating Synthetic Sensor Data to Facilitate Machine Learning Paradigm for Prediction of Building Fire Hazard. Fire Technol. https://doi.org/10.1007/s10694-020-01022-910.1007/s10694-020-01022-9 ↗
3. Peacock RD, Reneke PA and Forney GP (2019) CFAST—consolidated fire and smoke transport (Version 7) volume 2: user’s guide. Technical Note 1889v2, National Institute of Standards and Technology, Gaithersburg, MD, May 2019
4. Peacock RD, Reneke PA (2019) CFAST—consolidated fire and smoke transport (Version 7) volume 3: software development and model evaluation guide. Technical Note 1889v3, National Institute of Standards and Technology, Gaithersburg, MD, May 2019
5. Heskestad G., Delichatsios MA (1977) Environments of fire detectors—phase i: effect of fire size, ceiling height, and material, volume I: “Measurements” (NBS-GCR-77-86) (1977), Volume II: “Analysis”. (NBS-GCR-77-95), National Technical Information Service (NTIS), Springfield, VA
6. Geiman JA, Gottuk DT, Milke JA (2006) Evaluation of smoke detector response estimation methods: optical density, temperature rise, and velocity at alarm. J Fire Protect Eng 16(4)10.1177/1042391506060705 ↗
7. Iqbal N, Salley MH (2004) Fire dynamics tools (FDTs), quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program. NUREG 1805, U.S. Nuclear Regulatory Commission, Office of Nuclear Regulatory Research, Rockville, MD
8. Underwriters Laboratories Inc. (2016) ANSI/UL 268: standard for safety smoke detectors for fire alarm systems, Northbrook, IL
9. Dobbins RA, Mulholland GW, Bryner NP (1994) Comparison of a fractal smoke optics model with light extinction measurements. Atmos Environ 28:889–897. https://doi.org/10.1016/1352-2310(94)90247-X10.1016/1352-2310(94)90247-X ↗
10. Cleary TG, Chernovsky A, Grosshandler W, Anderson M (2000) Particulate entry lag in spot-type smoke alarms. Fire Saf Sci 6:779–790. https://doi.org/10.3801/iafss.fss.6-77910.3801/IAFSS.FSS.6-779 ↗