journal article·2005-04

Using Heat Release Rate to Assess Combustibility of Building Products in the Cone Calorimeter

Karen Carpenter, Marc Janssens

Fire Technology· Volume 41· Issue 2
Publisher page

Abstract

Building codes generally permit unlimited use of materials that contribute negligible quantities of heat in the event of a fire. These materials are referred to as non-combustible. Whether a material qualifies as being non-combustible is generally based on performance in a small-scale furnace test, or on its potential heat content measured in an oxygen bomb calorimeter. However, furnace and oxygen bomb methods to assess combustibility have serious limitations. The most significant limitations are that materials cannot be evaluated in their end-use configuration, that test conditions are not representative of real fire exposure conditions, and that the test results do not provide a realistic measure of the expected heat release rate. These limitations lead to the idea of exploring the use of small-scale heat release calorimeters to assess material combustibility. The Cone Calorimeter has emerged in recent years as the most widely used apparatus for this application. In this paper, an overview is presented of past efforts to assess combustibility based on heat release rate measurements. The main results of the most recent Cone Calorimeter round robin conducted in North America are discussed. It is concluded from the results of this round robin that the Cone Calorimeter is indeed suitable for measuring heat release rate from materials and products with low heat content. Limitations due to Cone Calorimeter specimen size can be alleviated by using a larger calorimeter, such as the Intermediate Scale Calorimeter or ICAL (ASTM E 1623.) However, more research is needed to extend the correlation between Cone Calorimeter and ICAL data to a wider range of materials. The biggest challenge is perhaps the implementation of a system to assess combustibility on the basis of heat release rate in the building codes. Implementation could consist of a classification system that is accepted as an alternative to the present prescriptive requirements and/or promoting the use of heat release rate data in performance-based design.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Combustion and Detonation Processes · Fire effects on concrete materials

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (28)

Show source-provided references
1. A. Ahonen, H. Weckman, and M. Yli-Penttilä, ?Application of Oxygen-Consumption Calorimetry to Non-Combustibility Testing,? Fire and Materials, vol. 9, 1985, pp. 135?144.10.1002/fam.810090306 ↗
2. A. Aikman, ?Degrees of Combustibility Integrated into an Objective-Based Model Building Code,? in Proceedings of the First NFPRF Fire Risk and Hazard Assessment Symposium, San Francisco, CA, June 26?28, 1996, National Fire Protection Research Foundation, Quincy, MA, 1996, pp. 79?91.
3. ASTM E 176-04: Standard Terminology of Fire Standards, ASTM Annual Book of Standards, vol. 04.07, ASTM, West Conshohocken, PA.
4. ASTM E 136-04: Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750^C, ASTM Annual Book of Standards, vol. 04.07, ASTM, West Conshohocken, PA.
5. ASTM E 1354-04: Standard Test Method for Heat and Visible Smoke Release Rates For Materials and Products Using an Oxygen Consumption Calorimeter, ASTM Annual Book of Standards, vol. 04.07, ASTM, West Conshohocken, PA.
6. ASTM E 1623-04: Standard Test Method for Determination of Fire and Thermal Parameters of Materials, Products, and Systems Using an Intermediate Scale Calorimeter (ICAL), Annual Book of Standards, vol. 04.07, ASTM, West Conshohocken, PA.
7. V. Babrauskas, W.H. Twilley, and W.J. Parker, ?Effects of Specimen Edge Conditions on Heat Release Rate,? Fire and Materials, vol. 17, 1993, pp. 51?63.10.1002/fam.810170202 ↗
8. V. Babrauskas, J. Urbas, and L. Richardson, ?Related Quantities. Part E. Non-Combustibility,? Chapter 8 in Heat Release in Fires, V. Babrauskas and S.J. Grayson (eds.), NY: Elsevier Applied Science, 1992, pp. 257?264.
9. ?CAN/ULC-S114-M80: Standard Test for Determination of Non-combustibility of Building Materials,? Underwriters? Laboratories of Canada, Scarborough, ON.
10. ?CAN/ULC-S135-92: Standard Method for Determination of Degrees of Combustibility of Building Materials Using an Oxygen Consumption Calorimeter (Cone Calorimeter),? Underwriters? Laboratories of Canada, Scarborough, ON.
11. C.H. Chen, L.S. Jang, M.Y. Lei, and S. Chou, ?A Comparative Study of Combustibility and Surafce Flammability of Building Materials,? Fire and Materials, vol. 21, 1997, pp. 271?276.10.1002/(SICI)1099-1018(199711/12)21:6<271::AID-FAM621>3.0.CO;2-1 ↗
12. ?EN 15302:2002. Fire Classification of Construction Products and Building Elements. Part 1. Classification Using Test Data from Reaction-to-Fire Tests,? European Committee for Standardization, Brussels, Belgium.
13. ?ISO 9705:1993. Fire tests-Reaction to Fire?-Full-Scale Room Test for Surface Products,? International Organization for Standardization, Geneva, Switzerland.
14. ?ISO 13943:1999. Fire safety?-Vocabulary,? International Organization for Standardization, Geneva, Switzerland.
15. ?ISO 1182:2002. Reaction to Fire Tests for Building Products?-Non-combustibility Test,? International Organization for Standardization, Geneva, Switzerland.
16. ?ISO 1716:2002. ?Reaction to Fire Tests for Building Products?-Determination of Gross Calorific Value,? International Organization for Standardization, Geneva, Switzerland.
17. ?ISO 5660-1:1993. Fire Tests-Reaction to Fire?-Rate of Heat Release from Building Products (Cone Calorimeter),? International Organization for Standardization, Geneva, Switzerland.
18. M.L. Janssens, ?Interlaboratory Cone Calorimeter Test Program,? ASTM Institute for Standards Research, Philadelphia, PA, 1994.
19. M.L. Janssens, ?Innovative Methods for Evaluating Combustibility of Materials and Assemblies,? in Proceedings of the First ASIAFLAM Conference, Kowloon, Hong Kong, March 15-16, 1995, Interscience Communications, London, England, 1995, pp. 397?407.
20. M. Janssens and J. Urbas, ?Comparison of Small and Intermediate Scale Heat Release Data,? in Interflam ?96, 7th International Fire Conference, March 26?28, 1996, Cambridge, England, C. Franks and S. Grayson (eds.), London, England: Interscience Communications Ltd. 1996, pp. 285?294.
21. NFPA 220: Standard on Types of Building Construction, Quincy, MA: National Fire Protection Association, 1999.
22. NFPA 259: Standard Test Method for Potential Heat of Building Materials, Quincy, MA: National Fire Protection Association, 2003.
23. L.R. Richardson, ?Determining Degrees of Combustibility of Building Materials?-National Building Code of Canada,? Fire and Materials, vol. 18, 1994, pp. 99?106.10.1002/fam.810180206 ↗
24. L.R. Richardson and M.E. Brooks, ?Combustibility of Building Materials,? Fire and Materials, vol. 15, 1991, pp. 131?136.10.1002/fam.810150305 ↗
25. E.E. Smith, ?An Experimental Determination of Combustibility,? Fire Technology, vol. 7, 1971, pp. 109?119.10.1007/BF02588951 ↗
26. Y. Tsuchiya and J.F. Mathieu, ?Measuring Degrees of Combustibility Using an OSU Apparatus and Oxygen Depletion Principle,? Fire Safety Journal, vol. 17, 1991, pp. 291?299.10.1016/0379-7112(91)90024-S ↗
27. L. Tsantaridis and B. Ostman, ?Communication: Retainer Frame Effects on Cone Calorimeter Results for Building Products,? Fire and Materials, vol. 17, 1993, pp. 43?46.10.1002/fam.810170108 ↗
28. J. Urbas, ?BDMC Interlaboratory Cone Calorimeter Test Program,? Fire and Materials, vol. 26, 2002, pp. 29?35.10.1002/fam.782 ↗