journal article·2006-10

Concrete for Tunnel Linings Exposed to Severe Fire Exposure

Lars Boström, Claus K. Larsen

Fire Technology· Volume 42· Issue 4
Publisher page

Abstract

The fire resistance with respect to temperature response and spalling have been experimentally determined for several different concrete qualities. The results show that some qualities perform relatively well even without any type of passive fire protection. Tests have also been made using protection in form of addition of polypropylene fibres as well as thermal barriers. Concrete with addition of polypropylene fibres perform very well. Although, there is still a question regarding the long term durability such as frost resistance and chloride penetration when polypropylene fibres are used. The tests made on concrete with thermal barriers were unsatisfactory since the products used in the tests had documentation on the performance but failed during these tests. A reason for this may be that the previous tests did not catch eventual problems with adhesion between the thermal barrier and the concrete. In the present study three different systems were tested and all failed. Although, when using mechanical bonding and reinforcement net two of the products (spray-on systems) worked well.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire effects on concrete materials · Fire dynamics and safety research · Structural Behavior of Reinforced Concrete

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (7)

Show source-provided references
1. prEN 1992-1-2, Eurocode 2: Design of concrete structures–Part 1–2: General rules–-Structural fir design, 2003.
2. Y. Anderberg and O. Pettersson, Structural Fire Design of Concrete Structures, (Brandteknisk Dimensionering av Betongkonstruktioner), T13:1992, Statens råd för byggnadsforskning, 1992 (in Swedish).
3. A. Lönnermark and H. Ingason, Large Scale Fire Tests in the Runehamar tunnel—Gas Temperature and Radiation, Int. Symp. on Catastrophic Tunnel Fires, Borås, Sweden, Nov. 20–21, 2003.
4. L. Boström, Innovative Self-Compacting Concrete–-Development of Test Methodology for Determination of Fire Spalling, SP Report 2004:06, Borås, Sweden, 2004.
5. H. Ingason, Time-Temperature Curves for X2000 and the Öresund Trains, Report P003814, Borås, 2000 (in Swedish).
6. I.R. Holt, “Is your Tunnel Protected against Fire,?”International Fire Protection, No. 16, November 2003.