journal article·2010-10Open access

Performance of Different Temperature Sensors in Standard Fire Resistance Test Furnaces

Mohamed A. Sultan

Fire Technology· Volume 46· Issue 4

Abstract

Defining a methodology for measuring temperature in fire resistance furnaces is a challenge. This paper presents and discusses the performance of six different types of temperature sensors in wall and floor fire resistance furnaces namely: the ASTM E119 shielded thermocouples, ISO 834 plate thermometers, directional flame thermometers, bare-bead thermocouples, Inconel grounded and ungrounded sheathed thermocouples. The Inconel grounded and ungrounded sheathed thermocouples provided comparable results to those of the bear-bead thermocouples and are most suitable when a fast response time is desirable. Because of the fast response time and good durability, grounded and ungrounded junction thermocouples are well-suited for use in controlling the temperature in fire resistance standard test furnaces. The predicted and measured incident heat flux in furnaces controlled by either the bare-bead or grounded and ungrounded sheathed thermocouples are in good agreement.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Advanced Sensor Technologies Research · Nuclear Engineering Thermal-Hydraulics

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (15)

Show source-provided references
1. ASTM E119-08, Standard methods of fire tests of building constructions and materials. ASTM, Philadelphia, PA
2. ISO 834-1, Fire resistance tests elements of building construction––part 1
3. CAN/ULC-S101-07, Standard methods of fire endurance tests of building construction and materials. ULC, Toronto, Ontario Canada
4. Wickström U (1997) The plate thermometer––practical aspects, SP-report 1997:28. Swedish National Testing and Research Institute
5. The European Standard EN 1363-1 (1999) Fire resistance tests––part 1: general requirements. European Committee for Standardization, rue de Stassart 36, B-1050 Brussels
6. Sultan MA (2008) Fire resistance furnace temperature measurements: plate thermometers versus shielded thermocouples. Fire Technol 42:253–26710.1007/s10694-006-8431-7 ↗
7. Sultan MA (2009) Comparisons of temperature and heat flux in furnaces controlled by different types of temperature sensors. Published online, J ASTM Int. 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959
8. Babrauskas V, Williamson RB (1978) Temperature measurement in fire test furnaces. Fire Technol 14(3)10.1007/BF01983057 ↗
9. Wickström U (2008) Adiabatic surface temperature and the plate thermometer for calculating heat transfer and controlling fire resistance furnaces. Fire safety science proceedings of ninth international symposium10.3801/IAFSS.FSS.9-1227 ↗
10. Longenbaugh RS et al (1990) Thermal response of a small scale cask-like test article to three different high temperature environments. Sandia National Laboratories Report to Federal Rail Administration, DOT/FRA/ORD-90/01
11. Keltner NR (2007) Directional flame thermometers: a tool for measuring thermal exposure in furnaces and improving control. Interflam 2007, proceedings of the eleventh international conference. Interscience Communications
12. Keltner N (2008) Private communication
13. OMEGA Engineering, The temperature handbook, vol 20, p A-7. OMEGA Engineering Inc., P.O. Box 4047, Stamford, CT 06907-0047, USA
14. Shorter GW, Harmathy TZ (1960) Fire research furnaces at the national research council, NRC 5732. National Research Council Canada, Ottawa, Ontario, Canada
15. Sultan MA, Denham M (1997) Harmonization of fire severity in standard fire resistance test furnaces. Fire safety sciences––proceedings of the fifth international symposium10.3801/IAFSS.FSS.5-1045 ↗