journal article·2018-01Open access

A Study of the Effect of Make-Up Air Velocity on the Smoke Layer Height with Symmetric Openings in Atrium Fires

Amir Rafinazari, George Hadjisophocleous

Fire Technology· Volume 54· Issue 1

Abstract

This paper presents full-scale test results and CFD modeling of smoke conditions in atrium fires in the case of symmetric make-up air opening arrangements. The atrium used for the experiments was equipped with a smoke management system capable of exhausting 132 m3/s. Thermocouple trees were installed to measure the temperature along the height of the atrium. The N-percentage method was used to determine the smoke interface height from the measured temperature profiles. Make-up air velocities of 1 m/s, 1.5 m/s and 2 m/s were selected to investigate the effect of make-up air velocity on the smoke interface height in the case of 4-side and 2-opposite side openings. The fire size varied from 1 MW to 5 MW to cover the effect of small, medium and large fires. FDS was also used to simulate the atrium fires in order to compare the predictions with the full-scale test results and evaluate the accuracy of the developed correlations. Results show that the limit of 1 m/s is too restrictive in the case of symmetric opening arrangements. A correlation is proposed based on the full-scale test results that can be used to modify the smoke layer height obtained using plume equations so that the effect of make-up air velocity on the smoke layer height is considered.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Evacuation and Crowd Dynamics · Fire Detection and Safety Systems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (19)

Show source-provided references
1. Rafinazari A, Hadjisophocleous G (2017) Full-scale tests and CFD modeling to investigate the effect of opening arrangement on smoke layer height in atrium fires. In: Harada K, Matsuyama K, Himoto K, Nakamura Y, Wakatsuki K (eds) Fire Science and Technology 2015. Springer, Singapore, pp 793–80010.1007/978-981-10-0376-9_81 ↗
2. Heskestad G (1988) Fire plume air entrainment according to two competing assumptions. In: Symposium (international) on combustion, vol 21(1), Elsevier, p 198810.1016/S0082-0784(88)80237-6 ↗
3. Klote JH, Ferreira MJ, Kashef A, Turnbull PG, Milke JA (2012) Handbook of smoke control engineering. American society of heating refrigerating and air-conditioning engineers
4. Cooper LY, Harkleroad M, Quintiere J, Rinkinen W (1982) An experimental study of upper hot layer stratification in full-scale multiroom fire scenarios. J Heat Transf 104:74110.1115/1.3245194 ↗
5. Hadjisophocleous G, Zhou J (2008) Evaluation of atrium smoke exhaust make-up air velocity. ASHRAE Trans 114(1)
6. Lougheed GD, Hadjisophocleous GV, McCartney C, Taber BC (1999) Large-scale physical model studies for an atrium smoke exhaust system Ashrae Trans 105:676
7. Hadjisophocleous GV, Fu Z, Lougheed GD (2002) Experimental study and zone modelling of smoke movement in a model atrium. ASHRAE Trans 108(2): 868–874
8. Chow WK (2009) Determination of the smoke layer interface height for hot smoke tests in big halls. J Fire Sci 27(2):125–14210.1177/0734904108096852 ↗
9. National Fire Protection Association (2011) NFPA 92: standard for smoke control systems. MA, USA
10. Rafinazari A, Hadjisophocleous G (2016) Full-scale tests and CFD modelling to evaluate the make-up air effects on the smoke conditions in atrium fires. In: The 14th international conference, Interflam 2016, London, UK, 4–6th July 2016. Interscience Communications, pp 1277–1287
11. Floyd JE, Forney GP, Hostikka S, McGrattan KB, Prasad K (2007) Fire dynamics simulator (version 3) user’s guide
12. Zhou J, Hadjisophocleous G (2008) Parameters affecting fire plumes. ASHRAE Trans 114(1)
13. Kerber S, Milke JA (2007) Using FDS to simulate smoke layer interface height in a simple atrium. Fire Technol 43(1): 45–7510.1007/s10694-007-0007-7 ↗
14. Gutiérrez-Montes C, Sanmiguel-Rojas E, Viedma A, Rein G (2009) Experimental data and numerical modelling of 1.3 and 2.3 MW fires in a 20 m cubic atrium. Build Environ 44(9):1827–183910.1016/j.buildenv.2008.12.010 ↗
15. Doheim RM et al (2014) The impact of atrium shape on natural smoke ventilation. Fire Saf J 63:9–1610.1016/j.firesaf.2013.11.005 ↗
16. Ayala P, Cantizano A, Gutiérrez-Montes C, Rein G (2013) Influence of atrium roof geometries on the numerical predictions of fire tests under natural ventilation conditions. Energy Build 65:382–39010.1016/j.enbuild.2013.06.010 ↗
17. National instruments (2003) LabVIEW user manual
18. McGrattan K, Hostikka S, Floyd JE (2010) Fire dynamics simulator (version 5), user’s guide. NIST Spec Publ 1019(5):1–186
19. Janssens M, Tran HC (1992) Data reduction of room tests for zone model validation. J Fire Sci 10(6):528–55510.1177/073490419201000604 ↗