Fire Scenarios for Multi-storey Façades with Emphasis on Full-Scale Testing of Wooden Façades
Source abstract
Abstract
This paper briefly reviews the main fire scenarios for exterior facade claddings on multi-storey buildings, together with available full-scale test procedures and performance requirements in different countries. It is obvious that there is no international agreement or approach on how to evaluate the fire safety of facade claddings. Two series of full-scale fire tests of wooden facades, in accordance with the Swedish SP Fire 105 test, are presented: one series for different proportions of untreated wood (partial wood and structural fire protection with a fire shield above the window), and another series for fire-retardant-treated wood. The results are compared with data from the intermediate scale Single Burning Item test and the small scale cone calorimeter test. A main conclusion is that SP Fire 105 is a useful tool to evaluate the fire behaviour of facade claddings, but it should be complemented with more objective measurements. Claddings with partial wood and the use of a fire shield above the window fulfil the requirements. Wood claddings treated with fire retardants (FR) may fulfil the requirements, if the amount of FR is high enough. It is also essential to demonstrate the weather durability of the FR treatment. Good agreement has been found with the other test methods used. The need to use fire stops behind multi-storey facade claddings to avoid the spread of fire in cavities is underlined.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Structural Analysis of Composite Materials · Flame retardant materials and properties
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (30)
Show source-provided references
1. Östman et al (2010) Fire safety in timber buildings—technical guideline for Europe. SP Report 2010:19, SP Technical Research Institute of Sweden, Stockholm
2. EN 13501-1. Fire classification of construction products and building elements—Part 1: Classification using test data from reaction-to-fire tests. European Standard
3. SP FIRE 105 (1994) External wall assemblies and façade claddings. Reaction to fire. Fire test method, Swedish National Testing and Research Institute, Issue No 5. SP Technical Research Institute of Sweden
4. Strömgren M, Albrektsson J, Johansson A, Almgren E (2013) Comparative analysis of façade regulations in the Nordic countries. In: Proceedings 1st international seminar for fire safety of façades, CSTB. MATEC web of conferences 9, 06004. www.matec-conferences.org10.1051/matecconf/20130901003 ↗
5. Loebus S, Werther N, Winter S (2013) Fire safety in timber-based element façade-systems. In: Proceedings 1st international seminar for fire safety of façades, CSTB, 2013. MATEC web of conferences 9, 06004. www.matec-conferences.org10.1051/matecconf/20130902007 ↗
6. Östman B, Voss A, Hughes A, Hovde PJ, Grexa O (2001) Durability of fire retardant treated wood at humid and exterior conditions. Review of literature. Fire Mater 25:95–10410.1002/fam.758 ↗
7. CEN/TS 15912 (2012) Durability of reaction to fire performance of FRT wood-based products in interior and exterior end-use applications, European Technical Specification
8. ASTM D 2898-94: Standard methods for accelerated weathering of fire-retardant-treated wood for fire testing
9. ISO 5660. Fire tests—reaction to fire—Part 1: Rate of heat release from building products. International standard
10. Östman B, Tsantaridis L (2011) Durability of the reaction to fire performance for FRT wood products in different end use applications—a ten years report. In: Proceedings of the 12th international conference on durability of building materials and components, XII DBMC, Porto, April 2011
11. Nystedt F (2011) Verifying alternatives in buildings with fire sprinkler systems. Department of Fire Safety Engineering and Systems Safety, Lund University, Report 3150
12. Nystedt F (2012) Case studies on the verification of fire safety design in sprinklered buildings. Department of Fire Safety Engineering and Systems Safety, Lund University, Report 7035
13. INSTA TS 950 (2014) Fire Safety Engineering—comparative method to verify fire safety design in buildings. Inter-Nordic Technical Specification
14. Hakkarainen T, Oksanen, T (2002) Fire safety assessments of wood. Fire Mater 26:7–2710.1002/fam.780 ↗
15. Korhonen T, Hietaniemi J (2005) Fire safety of wooden façades in residential suburb multi-storey buildings. In: VTT working paper 2, Espoo
16. Wade C (1995) Fire performance of external wall claddings under a performance-based building code. Fire Mater 19:127–13210.1002/fam.810190305 ↗
17. Lignum Dokumentation Brandschutz: 7.1 Außenwände, Konstruktion und Bekleidung. www.lignum.ch
18. Soja E, Wade C (2006) Flammability tests for external cladding on buildings (Chap. 4). In: V. B. Apte (ed.) Flammability testing of materials used in construction, transport and mining. Woodhead Publishing in Materials, Cambridge
19. EN 13823. Reaction to fire test for building products—building products excluding flooring—exposed to the thermal attack by a single burning item (SBI test). European Standard
20. Östman B, Mikkola E (2006) European classes for the reaction to fire performance of wood products. Holz Roh Werkstoff 64:327–33710.1007/s00107-006-0116-x ↗
21. ISO 13785. Reaction to fire tests for façades. Part 1: Intermediate-scale test. Part 2: Large scale test. International Standards Organization
22. ÖNORM B 3800-5 (2003) Fire behaviour of building materials and components—Part 5: Fire behaviour of façades—requirements, tests and evaluations
23. Arrêté du 10 septembre (1970) Classification des couvertures en materiaux combustibles par rapport au danger d’incendie resultant du feu exterieur
24. DIN 4102-20 (draft) (1998) Brandverhalten von Baustoffen und Bauteilen—Teil 1: Fassaden
25. BS 8414 (2005) Fire performance of external cladding systems
26. EOTA Technical Report N073 (2013) Large scale fire performance testing of external wall cladding systems. In preparation
27. Östman et al (2012) Fire safe timber buildings—Nordic-Baltic guideline version 3 (in Swedish). SP Report 2012:18, SP Technical Research Institute of Sweden, Stockholm
28. Östman B (2005) Fire performance of multi-storey wooden façade claddings. SP Report 2005:16, SP Technical Research Institute of Sweden, Stockholm
29. SP Test Reports (all in Swedish) (1999–2000) Report 98R1 3160: Fire testing of façade cladding. Wood laths; Report 98R1 3167 A, B, C and D: Fire testing of façade cladding. Non combustible areas and fire shield; Report R1 8505: Reference values; Report P001919 A, B and C: Fire testing of façade cladding. FRT wood panels. SP Technical Research Institute of Sweden, Borås
30. Ondrus J, Pettersson O (1986) Fire hazards of façades with externally applied additional thermal insulation. Full scale experiments, Lund Institute of Technology, Report LUTVDG/(TVBB-3025)