journal article·2016-11

Investigation of Fire Extinguishment in Large Facilities based on Physical Scaling, Modeling and Testing

Hong-Zeng Yu

Fire Technology· Volume 52· Issue 6
Publisher page

Abstract

An investigation was conducted to determine the feasibility of extending the total flooding water mist protection previously developed for a 7.47 × 7.47 × 7.47-m3 ignitable liquid dispensing facility to a larger building, for a longer but acceptable fire extinguishing time. The targeted building height and door opening were 7.62 m and 3.81 × 3.81 m2, respectively. Same as for the 7.47-m cubic facility, the fire challenge was the combination of a cascading heptane fire spilling from the top of a fuel tank and the resulting shielded pool fire on the floor. The Froude-based scaling methodology and a well-stirred reactor model were used to assess the maximum building size and associated water mist requirement for a 0.48-scale mockup of the 7.62-m high facility, under the constraint of meeting the designated fire extinguishment time. A series of fire tests was then conducted in the 0.48-scale mockup to verify that the fire could indeed be extinguished within the designated duration for the determined building size and protection requirement. In general, it took less time to extinguish the fire as the water mist discharge rate was increased. The water mist sprays deployed in the door opening tended to reduce the fire extinguishment time by reducing air flow through the door opening, but not significantly in this investigation. However, the deployment of water mist sprays in the door opening is highly recommended to confine the spill fire within the protected building. The tests also showed that it took longer time to extinguish the fire as the fire was closer to the door opening. Based on the 0.48-scale test results and scaling relationships, the water mist protection requirement and corresponding fire extinguishment time for the 7.62-m high facility were projected for a building floor area of 580 m2.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Evacuation and Crowd Dynamics · Fire dynamics and safety research · Fire Detection and Safety Systems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (11)

Show source-provided references
1. Yu H-Z (2013) Physical scaling of water mist protection for ignitable liquid cut-off rooms. J Fire Prot Eng 23(3):157–17610.1177/1042391513490298 ↗
2. Yu H-Z (2012) Froude-modeling-based general scaling relationships for fire suppression by water sprays. Fire Saf J 47:1–710.1016/j.firesaf.2011.09.006 ↗
3. Yu H-Z (2011) Physical scaling of water mist suppression of pool fires in enclosures. In: Proceedings of the 10th international symposium on fire safety science, International Association of Fire Safety Science, pp 19–2410.3801/IAFSS.FSS.10-145 ↗
4. Yu H-Z, Kasiski R, Daelhousen M (2015) Characterization of twin-fluid (water mist and inert gas) fire extinguishing systems by testing and modeling. Fire Technol 51:923–950. doi: 10.1007/s10694-014-0428-z10.1007/s10694-014-0428-z ↗
5. Zabetakis M (1965) Flammability Characteristics of Combustible Gases and Vapors. Bulletin 627, U.S. Department of the Interior, Bureau of Mines10.2172/7328370 ↗
6. Roberts AF, Quince BW (1973) A limiting condition for the burning of flammable liquids. Combust Flame 20:245–25110.1016/S0010-2180(73)80178-6 ↗
7. Macek A (1979) Flammability limits: a re-examination. Combust Sci Technol 21:43–5210.1080/00102207908946917 ↗
8. Pitts WM (2009) Improved understanding of thermal agent fire suppression mechanisms from detailed chemical kinetic modeling with idealized surrogate agents, In: Proceedings of the 32nd symposium (international) on combustion, The Combustion Institute, pp 2599–260610.1016/j.proci.2008.06.210 ↗
9. Foster AM, Swain MJ, Barrett R, D’Agaro P, James SJ (2006) Effectiveness and optimum jet velocity for a plane jet air curtain used to restrict cold room infiltration. Int J Refrig 29:692–69910.1016/j.ijrefrig.2005.12.011 ↗
10. Lefebvre AH (1989) Atomization and spray. Hemisphere Publishing Corporation, New York
11. ASME (2007) ASME boiler & pressure vessel code—II Part D: properties (customary) materials, The American Society of Mechanical Engineers, New York