Three Different Fire Suppression Approaches Used by Fire and Rescue Services
Source abstract
Abstract
This paper describes the relationship between the water flow rate applied by the Fire and Rescue Services (FRS) and the area of a fire; the limitations of the FRS in terms of water flow rate; and the most effective use of firefighting water across a broad range of fire areas. The paper is based on five sets of data gained by the FRS at the fire scene, in total almost 6000 fires. It shows a fundamental difference in fighting a small fire compared to fighting a large one. It also shows that the relationship between applied water flow rate and fire area is not best described by a continuous power function. It distinguishes between three different approaches or modes of firefighting: a standard nozzle approach (fires up to 20–50 m2, depending on context), a perimeter approach (fires up to 200–500 m2, depending on context) and a maximum flow approach (fires larger than 200–500 m2, depending on context). The transition between the approaches varies between the five data sets and can be distinguished using the optimum flow density (5.4–6.0 l/m2 min) or the water flow density giving the smallest total volume and the critical water flow density (3.5–4.0 l/m2 min). The two transitions vary with the context; they are not physical constants (the numbers corresponds to the most recent studies of Metro and County FRS). The study validates the strategic considerations that attack is more demanding than containment, that one should ensure containment and then attack; and that the earlier response, the better result.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire effects on concrete materials · Fire dynamics and safety research · Disaster Management and Resilience
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (19)
Show source-provided references
1. Fredholm L (1991) The development of rescue tactics, analysis and proposed methods, FOA report C 50089-5.3, ISSN 0347-7665, National Defence Research Establishment, Ursvik
2. von Clausewitz C (1832) On war, available in several editions, the first in 1832
3. Benfer ME, Scheffey JL (2015) Evaluation of fire flow methodologies, Springer, New York10.1007/978-1-4939-2889-7 ↗
4. Särdqvist S (1999) Fire brigade use of water. In: Interflam, ‘99, proceedings of eighth international conference, vol. 1, Interscience Communications Ltd. pp 675–683
5. Linder KW (1991) Water supply requirements for fire protection. In: Cote AE (ed) Fire protection handbook, 17th edition. NFPA, Quincy, pp 5-40–5-47
6. NFPA 13 (2016) Standard for the installation of sprinkler systems, NFPA, Quincy
7. Brunacini AV (1985) Fire command. National Fire Protection Association, Quincy
8. Grimwood P, Sanderson IA (2015) The County/Metro research into fire-fighting suppressive capacity and the impact on building fire damage at > 5000 UK building fires, 2009–2012. Fire Saf J 71:238–24710.1016/j.firesaf.2014.11.027 ↗
9. Särdqvist S, Holmstedt G (1998) Correlation between firefighting operation and fire area: analysis of statistics. Fire technology. 36(2):2000
10. Särdqvist S, Real fire data, fires in non-residential premises in London 1994–1997, Department of Fire Safety Engineering, Lund University, Sweden, Report 7003
11. Baldwin R (1972) Use of water in the extinction of fires by brigades. Inst Fire Eng Q 31(82):163–168
12. Thomas PH (1959) Use of water in the extinction of large fires. Inst Fire Eng Q 19(35):130–132
13. Kerber S (2012) Analysis of changing residential fire dynamics and its implications on firefighter operational timeframes, Fire Technol 48(4):865–89110.1007/s10694-011-0249-2 ↗
14. Särdqvist S, Holmstedt G (2001) Water for manual fire suppression. J Fire Prot Eng, 11(4), 209–231.10.1177/104239101400934333 ↗
15. Rasbach A (1985) The extinction of fire with plain water: a review. In: Fire safety science: proceedings of the first international symposium, pp 1145–1163
16. Grimwood P, Sanderson IA (2015) A performance based approach to defining and calculating adequate firefighting water using s.8.5 of the design guide BS PD 7974:5:2014 (fire service intervention). Fire Saf J 78:155–16710.1016/j.firesaf.2015.08.007 ↗
17. Särdqvist S, Svensson S (2001) Fire tests in a large hall, using manually applied high- and low-pressure water sprays. Fire Sci Technol 21(1): 1–1710.3210/fst.21.1 ↗
18. HM Government (2013) Approved document B: fire safety—volume 2: buildings other than dwellinghouses, B3 Section 8, Table 12
19. Grimwood P (1992) Fog attack, FMJ Publications, Redhill