Using Sensor Signals to Analyze Fires
Source abstract
Abstract
Building fire sensors are capable of supplying substantially more information to the fire service than just the simple detection of a possible fire. Nelson, in 1984, recognized the importance of tying all the building sensors to a smart fire panel [1]. In order to accomplish a smart fire panel configuration such as envisioned by Nelson, algorithms must be developed that convert the analog/digital signals received from sensors to the heat release rate (HRR) of the fire. Once the HRR of the fire is known, a multiroom zone fire model can be used to determine smoke layers and temperatures in the other rooms of the building. This information can then be sent to the fire service providing it with an approximate overview of the fire scenario in the building. This paper will describe a ceiling jet algorithm that is being developed to predict the heat release rate (HRR) of a fire using signals from smoke and gas sensors. The prediction of this algorithm will be compared with experiments. In addition, an example of the predictions from a sensor-driven fire model, SDFM, using signals from heat sensors, will be compared with measurements from a full-scale, two-story, flashover townhouse fire.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Evacuation and Crowd Dynamics · Fire dynamics and safety research · Fire Detection and Safety Systems
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (16)
Show source-provided references
1. H.E. Nelson, “Functional Programming/Research Planning for High Technology Federal Office Buildings,” National Institute of Standards and Technology, NBSIR 84–2828, 1984, pp. 1–28.
2. W.D. Davis and P. Reneke, “Predicting Smoke Concentration in the Ceiling Jet,” National Institute of Standards and Technology, NISTIR 6480, 2000, pp. 1–12.
3. G. Heskestad, “Engineering Relations for Fire Plumes,” Fire Safety J., vol. 7, 1984, pp. 25–32.10.1016/0379-7112(84)90005-5 ↗
4. R.L. Alpert, “Turbulent Ceiling-Jet Induced by Large-Scale Fires,” Combustion Science and Technology, vol. 11, 1975, pp. 197–213.10.1080/00102207508946699 ↗
5. Y. Yamauchi, “Prediction of Response Time of Smoke Detectors in Enclosure Fires,” National Institute of Standards and Technology, @ NBSIR 88–3707, 1988, pp. 1–46.10.6028/NBS.IR.88-3707 ↗
6. R.L. Alpert, “Calculation of Response Time of Ceiling-Mounted Fire Detectors,” Fire Technology, vol. 8, 1972, pp. 181–195.10.1007/BF02590543 ↗
7. W.D. Davis, T. Cleary, M. Donnelly, and S. Hellerman, “Predicting Smoke and Carbon Monoxide Concentration in the Ceiling Jet in the Presence of a Smoke Layer,” National Institute of Standards and Technology, NISTIR 6976, 2003, pp. 1–34.10.6028/NIST.IR.6976 ↗
8. W. Grosshandler, “Toward the Development of a Universal Fire Emulator-Detector Evaluator,” Fire Safety J., vol. 29, 1997, pp. 113–128.10.1016/S0379-7112(96)00031-8 ↗
9. G.W. Mulholland and C. Croarkin, “Specific Extinction Coefficient of Flame Generated Smoke,” Fire and Materials, vol. 24, 2000, pp. 227–230.10.1002/1099-1018(200009/10)24:5<227::AID-FAM742>3.0.CO;2-9 ↗
10. A. Tewarson, “Generation of Heat and Chemical Compounds in Fires,” The SFPE Handbook of Fire Protection Engineering, NFPA, 1995, pp. 3–53–3–124.
11. J.S. Newman and J. Steciak, “Characterization of Particulates from Diffusion Flames,” Combustion and Flame, vol. 67, 1987, pp. 55–64.10.1016/0010-2180(87)90013-7 ↗
12. M.E. Kounalakis, Y.R. Sivathanu, and G.M. Faeth, “Structure and Radiation Properties of Turbulent Nonluminous and Luminous Diffusion Flames,” NIST Grant 60nanb5d0576, 1988, pp. 1–78.
13. L. Orloff, J. de Ris, and M.A. Delichatsios, “Radiation From Buoyant Turbulent Diffusion Flames,” Factory Mutual Research Corporation, FMRC J. I. OTOJ7.BU, 1991, pp. 1–16.10.1080/00102209208951852 ↗
14. H.A. Becker and D. Liang, “Total Emission of Soot and Thermal Radiation by Free Turbulent Diffusion Flames,” Combustion and Flame, vol. 44, 1982, pp. 305–318.10.1016/0010-2180(82)90080-3 ↗
15. W.D. Davis, “The Zone Fire Model JET: A Model for the Prediction of Detector Activation and Gas Temperature in the Presence of a Smoke Layer,” National Institute of Standards and Technology, NISTIR 6324, 1999, pp. 1–51.10.6028/NIST.IR.6324 ↗
16. R.S. Levine and H.E. Nelson, “Full Scale Simulation of a Fatal Fire and Comparison of Results with Two Multiroom Models Volume II—DATA,” National Institute of Standards and Technology, NISTIR 90–4268, 1990, pp. 1–125.10.6028/NIST.IR.90-4268 ↗