journal article·2012-07

Development of a Cup Burner Apparatus for Fire Suppression Evaluation of High-Expansion Foams

James W. Fleming, Ronald S. Sheinson

Fire Technology· Volume 48· Issue 3
Publisher page

Abstract

We developed a bench-scale high-expansion aqueous foam generator and integrated it into a traditional cup burner apparatus. Foam expansion ratios ranging from 50:1 to 590:1 could be achieved using air flow rates from 16 l/min to 38 l/min and liquid foam solution flow rates of 50 ml/min to 140 ml/min. The flow rates, foam expansion ratios, and cup burner flame extinction behavior with nitrogen provide a suitable bench-scale platform for controlled, systematic investigations of foam/flame interactions for a range of foam properties. Foams with an expansion ratio of 200:1 contain 81% water by mass. When evaporated completely, this amount of water should be insufficient to extinguish propane flames in oxidizer streams with 60% oxygen based on extinction of these flames by water mist. However, the 200:1 foam easily extinguishes a propane flame even in 100% oxygen.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Wind and Air Flow Studies · Combustion and flame dynamics

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (6)

Show source-provided references
1. Luers AC, Back GG, Gottuk DT, Scheffey JL, Darwin RL, Satterfield DB (2007) Joint High Speed Vessel Mission Bay Ordnance Stowage Preliminary Fire Hazard Analysis. Naval Sea Systems Command. Washington, DC
2. Back GG, Forssell EW, Wakelin AJ, Beene D, Nash L (2007) An Evaluation of Total Flooding High Expansion Foam Fire Suppression Systems for Machinery Space Applications. Fire Technol 42:187–210. doi: 10.1007/s10694-006-8432-610.1007/s10694-006-8432-6 ↗
3. Ananth R, Farley JP (2009) Suppression dynamics of a co-flow diffusion flame with high expansion aqueous foam. J Fire Sci. doi: 10.1177/073490410934103010.1177/0734904109341030 ↗
4. Fisher BT, Awtry AR, Sheinson RS, Fleming JW (2007) Flow Behavior Impact on the Suppression Effectiveness of Sub-10-μm Water Drops in Propane/air Co-flow Non-premixed Flames. Proc Combust Inst 31:2731-2739. doi: 10.1016/j.proci.2006.07.02310.1016/j.proci.2006.07.023 ↗
5. Ananth R and Mowrey RC (2008) Ultra-Fine Water Mist Extinction Dynamics of a Co-Flow Diffusion Flame. Combust Sci and Tech 180:1659–1692. doi: 10.1080/0010220080219756910.1080/00102200802197569 ↗
6. Senecal JA (2005) Flame Extinguishing in the Cup-burner by Inert Gases. Fire Safety Journal 40:579–591. doi: 10.1016/j.firesaf.2005.05.00810.1016/j.firesaf.2005.05.008 ↗