Firefighter Nozzle Reaction
Source abstract
Abstract
Nozzle reaction and hose tension are analyzed using conservation of fluid momentum and assuming steady, inviscid flow and a flexible hose in frictionless contact with the ground. An expression that is independent of the bend angle is derived for the hose tension. If this tension is exceeded owing to anchor forces, the hose becomes straight. The nozzle reaction is found to equal the jet momentum flow rate, and it does not change when an elbow connects the hose to the nozzle. A forward force must be exerted by a firefighter or another anchor that matches the forward force that the jet would exert on a perpendicular wall. Three reaction expressions are derived, allowing it to be determined in terms of hose diameter, jet diameter, flow rate, and static pressure upstream of the nozzle. The nozzle reaction predictions used by the fire service are 56% to 90% of those obtained here for typical firefighting hand lines. Sharing these findings with the fire protection community can improve the safety of firefighters.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Fire dynamics and safety research · Occupational Health and Performance · Fire Detection and Safety Systems
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (30)
Show source-provided references
1. [1] Purington RG (1974) Fire fighting hydraulics. McGraw-Hill, New York, p 368
2. [2] Fornell DP (1991) Fire stream management handbook. PenWell, Saddle Brook, p 223
3. [3] Wieder MA (2005) Fire service hydraulics and water supply. Fire Protection Publications, Stillwater, p 248
4. Wieder MA (2008) Fire streams. In: Cote AE, Fire protection handbook. NFPA, Quincy, pp 13–23
5. [5] Karter MJ (2013) Patterns of firefighter fireground injuries. NFPA, Quincy
6. Rulseh TJ (2011) A fatality involving a waterjet nozzle provides a lesson in safety diligence when cleaning sewers. Cleaner Magazine, Nov, p 22
7. [7] Mach E (1919) The science of mechanics: a critical and historical account of its development. Open Court, Chicago, p 299
8. [8] Oertel H (2010) Prandtl—essentials of fluid mechanics. Springer, New York, p 9310.1007/978-1-4419-1564-1 ↗
9. Feynman RP (1985) Surely you’re joking. Norton, New York, pp 63–65
10. [10] Fay JM (1994) Introduction to fluid mechanics. MIT Press, Cambridge, p 194
11. [11] Lautrup B (2011) Physics of continuous matter. CRC, Boca Raton, pp 357–35810.1201/9781439894200 ↗
12. [12] Theobald JJ (1946) Hydraulics for firemen, with problems and solutions. Barnes, New York, p 31
13. [13] Crapo WF (2017) Fire protection hydraulics and water supply. Jones and Bartlett, Burlington, p 151
14. [14] Nazarenko S (2015) Fluid dynamics via examples and solutions. CRC Press, Boca Raton, pp 20–35
15. [15] Vera F, Rivera R, Núñez C (2015) Letter to editor: backward reaction force on a fire hose, myth or reality? Fire Technol 51:1023–102710.1007/s10694-014-0430-5 ↗
16. Krishnakumar CK, Atallah S, Borows KA (1991) Development of a flow modifier for reducing the reaction force of firefighting nozzles. US Air Force Report ESL-TR-91-30110.21236/ADA591503 ↗
17. Alexandrou AN (2001) Principles of fluid mechanics. Prentice Hall, Upper Saddle River, p 126
18. [18] Shames IH (2003) Mechanics of fluids. McGraw-Hill, New York, p 195
19. [19] Crowe CT, Elger DF, Roberson JA (2005) Engineering Fluid Mechanics. Wiley, Hoboken, p 194
20. [20] Graebel WP (2001) Engineering fluid mechanics. Taylor and Francis, New York, p 155
21. [21] White FM (2016) Fluid mechanics. McGraw-Hill, New York, p 171
22. [22] Warren JW (1975) Forces on a hose. Phys Educ 10:327–32810.1088/0031-9120/10/4/116 ↗
23. [23] Albertson ML, Barton JR, Simons DB (1960) Fluid mechanics for engineers. Prentice-Hall, Englewood Cliffs, p 114
24. AWG Fittings GmbH (2016) Fire and rescue catalog. http://www.awg-fittings.com/fileadmin/catalogue/AWG/#12 . Accessed 24 Jan 2017
25. POK (2016) Firefighting equipment catalog. http://www.pok.fr/en/catalogues . Accessed 24 Jan 2017
26. Fang J (2011) Effect of nozzle design on reaction thrust and spray dynamics. M.S. Thesis, University of California, Davis
27. [27] NFPA 1410 (2015) Standard on training for initial emergency scene operations. NFPA, Quincy
28. Sicking L (2002) How to calculate nozzle reaction. United States Forest Service. http://www.fs.fed.us/eng/pubs/html/02511318/02511318.htm . Accessed 24 Jan 2017
29. Nelson ME (2003) Vindicator nozzle and hose evaluation report. Montgomery County Maryland Fire and Rescue Service. http://www.1ststriketech.com/Testimonies/MontgomeryCountyReport.pdf . Accessed 24 Jan 2017
30. [30] Vestal JN, Bridge EA (2010) A quantitative approach to selecting nozzle flow rate and stream, part 1. Fire Eng 163:10