journal article·2008-09

Analysis of Hold Time Models for Total Flooding Clean Extinguishing Agents

Todd M. Hetrick

Fire Technology· Volume 44· Issue 3
Publisher page

Abstract

This study documents the experimental results of a research program designed to evaluate the validity of the widely published hold time prediction models found in NFPA 2001, Annex C and ISO 14520-1, Annex E. The models discussed in these standards obtain a measure of the equivalent leakage area, which, when coupled with ‘worst case’ assumptions, can be used to determine the minimum hold time. Three hold time prediction theories are adopted from these standards for validation; a wide descending interface model as implemented in ISO 14520-1 and two sharp descending interface models from the 2004 and 2008 publications of NFPA 2001. The experimental program is comprised of 15 tests conducted in a 103 m3 test enclosure. Three commercially available clean agents are selected to span a wide range of agent vapor densities including FK-5-1-12, HFC-125, and IG-541. A series of holes were drilled through enclosure boundaries at upper and lower elevations which were opened or closed as a means of regulating the amount of leakage area for any given test. Vertical profiles of agent concentration and ambient pressure are used to evaluate the agent concentration distribution, rates of agent draining, and the effective lower leakage fraction. A non-dimensional hold time is used to compare experimental results involving differing agent types and leakage areas. Results show that empirical values of the hold time are up to 50% longer than the theoretical hold time predictions when evaluated as the time to reduce the agent concentration to half its initial value. When evaluated as a 15% drop in concentration the model validity is significantly reduced. Under this condition, empirical hold time values are up to 50% shorter than the predictions of the sharp descending interface models and up to 100% longer than the wide descending interface model.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Water Systems and Optimization

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (11)

Show source-provided references
1. Dewsbury J, Whiteley RA (2000) Review of fan integrity testing and hold time standards. Fire Technol 36(4), 249–26510.1023/A:1015427130420 ↗
2. DiNenno PJ, Forssell EW (1989). Evaluation of the door fan pressurization leakage test method applied to Halon 1301 total flooding systems. J Fire Protect Eng, 1(4), 131–14010.1177/104239158900100403 ↗
3. Mowrer F (2006) Analysis of vapor density effects on hold times for total flooding clean extinguishing agents. In: Halon options technical working conference, 16th proceedings, Albuquerque, New Mexico, May 2006, pp 1–12
4. O’Rourke ST (2005) Analysis of hold times for gaseous fire suppression agents in total flooding applications. Master thesis, University of Maryland, College Park MD
5. Dewsbury J, Whiteley RA (2000) Extensions to standard hold time calculations. Fire Technol 36(4), 267–27810.1023/A:1015479114491 ↗
6. Emmons HW (2002) Vent flows, chapter 2–3. In: The SFPE handbook of fire protection engineering, 3rd edn. NFPA, Quincy, MA
7. Saum D, Saum A, Messing M, Hupman J (1988) Pressurization air leakage testing for Halon 1301 enclosures. In: Substitutes and alternatives to chlorofluorocarbons and Halons. Washington, DC
8. ISO 14520-1 (2006) Gaseous fire extinguishing systems – physical properties and system design – part 1: general requirements. International Standards Organization, Geneva, Switzerland, Annex E
9. NFPA 2001 (2008) Standard on clean agent fire extinguishing systems. National Fire Protection Association, Quincy, MA, Annex C
10. NFPA 2001 (2004) Standard on clean agent fire extinguishing systems. National Fire Protection Association, Quincy, MA, Annex C
11. Genge C (2005) Preventing excessive enclosure pressures during clean agent discharges. In: Halon options technical working conference, 15th proceedings, Albuquerque, New Mexico, May, 2005, pp 1–16