journal article·2018-01

Effects of Ventilation and Water Spray in a Model-Scale Tunnel Fire

Chin-Feng Chen, Chi-Min Shu, San-Ping Ho, Hsiang-Cheng Kung, Shen-Wen Chien

Fire Technology· Volume 54· Issue 1
Publisher page

Abstract

At the present time, eight new long tunnels are currently being constructed in Taiwan and plan to utilize sidewall sprinkler nozzles to conduct fire protection. To explore the effect of ventilation and water spray on tunnel fires, this research used a 1/5.5 model scale tunnel to perform experiments, while using a heptane oil pan of 0.45 m diameter as the fire source. Under five different ventilation velocities, the cooling effects of water spray on tunnel fires was discussed while controlling the water density at 2.3 mm/min. The critical velocity without water spray was 1.24 m/s, which fits empirical equations by past research. Under a ventilation velocity of 0.87 m/s, the smoke backlayering would be 2 m without water spray, while none was present with water spray. Overall quantitative analysis shows the significance of water spray in affecting backlayering, and it can be acknowledged that water spray can prevent backlayering from larger fires under the same velocity. This research used visual and temperature measurement methods to determine the location of backlayering, and it is recommended that maximum temperature gradient be used in future research as the basis for smoke backlayering location.
Source: openaire · Quality: candidate unverified · Source record ↗

Research context

OpenAlex topics: Fire dynamics and safety research · Fire effects on ecosystems · Evacuation and Crowd Dynamics

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (27)

Show source-provided references
1. PIARC (1999) Fire and smoke control in road tunnels. PIARC Committee C5 on Road Tunnels
2. PIARC (2008) Road tunnels: an assessment of fixed fire fighting systems. PIARC Technical Committee C3.3 Road Tunnel Operations
3. National Fire Protection Association (2004) NFPA 502: standard for road tunnels, bridges, and other limited access highways. National Fire Protection Association, Quincy, MA, USA
4. National Fire Protection Association (2008) NFPA 502: standard for road tunnels, bridges, and other limited access highways. National Fire Protection Association, Quincy, MA, USA
5. One stop shop in structural fire engineering. http://www.mace.manchester.ac.uk/project/research/structures/strucfire/CaseStudy/HistoricFires/InfrastructuralFires/mont.htm . Accessed 31 Jan 2017
6. National Fire Protection Association (2011) NFPA 502: standard for road tunnels, bridges, and other limited access highways. National Fire Protection Association, Quincy, MA, USA
7. Lönnermark A, Ingason H (2003) Large scale fire tests in the Runehamar tunnel-gas temperature and radiation. In: International symposium on catastrophic tunnel fires (CTF), SP Swedish National Testing and Research Institute, Borås, Sweden
8. Studiengesellschaft Stahlanwendung e.V Dusseldorf (1995) Fires in transport tunnels: report on full-scale tests, EUREKA-Project EU 499: FIRETUN
9. Royal Institute of Engineers (1993) Ventilation of road tunnels, Netherlands
10. Haack A (1998) Fire protection in traffic tunnels: resume of EUREKA research project EU 499 FIRETUN. In: Tunnel structures, IABSE Colloquium, Stockholm
11. Carvel RO, Beard AN, Jowitt PW, Drysdale DD (2004) The influence of tunnel geometry and ventilation on the heat release rate of a fire. Fire Technol 40:5–2610.1023/B:FIRE.0000003313.97677.c5 ↗
12. Cheong MK, Cheong WO, Leong KW, Lemaire AD, Noordijk LM (2014) Heat release rate of heavy goods vehicle fire in tunnels with fixed water based fire-fighting system. Fire Technol 50:249–26610.1007/s10694-013-0367-0 ↗
13. Ingason H, Li YZ, Appel G, Lundström U, Becker C (2016) Large scale tunnel fire tests with large droplet water-based fixed fire fighting system. Fire Technol 52:1539–155810.1007/s10694-015-0479-9 ↗
14. Blanchard E, Boulet P, Desanghere S, Cesmat E, Meyrand R, Garo JP, Vantelon JP (2012) Experimental and numerical study of fire in a midscale test tunnel. Fire Saf J 47:18–3110.1016/j.firesaf.2011.09.009 ↗
15. Li YZ, Ingason H (2014) Position of maximum ceiling temperature in a tunnel fire. Fire Technol 50:889–90510.1007/s10694-012-0309-2 ↗
16. Li YZ, Fan CG, Ingason H, Lönnermark A, Ji J (2016) Effect of cross section and ventilation on heat release rates in tunnel fires. Tunn Undergr Space Technol 51:414–42310.1016/j.tust.2015.09.007 ↗
17. Oka Y, Atkinson GT (1995) Control of smoke flow in tunnel fires. Fire Saf J 25(4):305–32210.1016/0379-7112(96)00007-0 ↗
18. Wu Y, Bakar MZA (2000) Control of smoke flow in tunnel fires using longitudinal ventilation systems—a study of the critical velocity. Fire Saf J 35(4):363–39010.1016/S0379-7112(00)00031-X ↗
19. Zhong W, Li Z, Wang T, Liang T, Liu Z (2015) Experimental study on the influence of different transverse fire locations on the critical longitudinal ventilation velocity in tunnel fires. Fire Technol 51:1217–123010.1007/s10694-015-0461-6 ↗
20. Ingason H (2008) Model scale tunnel tests with water spray. Fire Saf J 43(7):512–52810.1016/j.firesaf.2007.12.002 ↗
21. Li YZ, Ingason H (2013) Model scale tunnel fire tests with automatic sprinkler. Fire Saf J 61:298–31310.1016/j.firesaf.2013.09.024 ↗
22. Ko YJ, Hadjisophocleous GV (2013) Study of smoke backlayering during suppression in tunnels. Fire Saf J 58:240–24710.1016/j.firesaf.2013.03.001 ↗
23. Sun J, Fang Z, Tang Z, Beji T, Merci B (2016) Experimental study of the effectiveness of a water system in blocking fire-induced smoke and heat in reduced-scale tunnel tests. Tunn Undergr Space Technol 56:34–4410.1016/j.tust.2016.02.005 ↗
24. TANFB (2013) Fire incident report at south 26K of Hsueh-Shan highway tunnel. Taiwan Area National Freeway Bureau. MOTC, ROC
25. Heskestad G (2002) Scaling the interaction of water sprays and flames. Fire Saf J 37(6):535–54810.1016/S0379-7112(02)00012-7 ↗
26. Gottuk DT, White DA (2008) Liquid fuel fires. The SFPE handbook of fire protection engineering, 4th edn. Society of Fire Protection Engineers, Quincy, pp 2–350
27. Ura F, Kawabata N, Tanaka F (2014) Characteristics of smoke extraction by natural ventilation during a fire in a shallow urban road tunnel with roof openings. Fire Saf J 67:96–10610.1016/j.firesaf.2014.05.009 ↗