Subjective Response to the Conditions of Audible Fire Alarm Signals Through a Jury Evaluation Test
Source abstract
Abstract
The main purpose of an audible fire alarm signal is to notify occupants of the presence of signs of a fire and to promote escape behavior, such as immediate evacuation. This study investigates audible fire alarm signal conditions that promote the most appropriate escape behavior. Four standard signals—alarm bell, horn, chime, and electronic siren—were selected as the fire alarm signals. Furthermore, a temporal-three pattern, recorded female voice, and transmitted signal were applied to each of the four signals. Using these signals, a jury evaluation test was conducted for a total of 76 participants between 19 and 36 years of age. The recollection, identification, and perceived urgency of each signal, along with the conditions that promote and appropriate escape behavior, were statistically assessed. For each signal condition, frequency analysis, correlation analysis, independent sample t-tests, and one-way analysis of variance were performed. Results indicate that there was a correlation between signal identification and appropriate escape behavior. Furthermore, an alarm bell signal with a recorded female voice was determined to be the most appropriate fire alarm signal.
Source: openaire · Quality: candidate unverified · Source record ↗
Research context
OpenAlex topics: Evacuation and Crowd Dynamics · Noise Effects and Management · Hearing Loss and Rehabilitation
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (22)
Show source-provided references
1. Hasofer AM, Bruck D (2004) Statistical analysis of response to fire cues. Fire Saf J 39:663–68810.1016/j.firesaf.2004.06.002 ↗
2. Thomas I, Bruck D (2010) Awakening of sleeping people: a decade of research. Fire Technol 46:743–76110.1007/s10694-008-0065-5 ↗
3. The National Law Information Center (2019) Fire safety standard for emergency alarm system and Stand Alone Smoke Detector (NFSC 201). Ministry of Government Legislation, Republic of Korea
4. NFPA 72, National fire alarm and signaling code. (2019 Edition)
5. British Standards Institution (2002) Fire detection and fire alarm system for buildings, BS 5839: Part 1. London, UK.
6. Sultan MA, Halliwell RE (1990) Optimum location for fire alarms in apartment buildings. Fire Technol 26:342–35610.1007/BF01293078 ↗
7. Bruck D, Horasan M (1995) Non-arousal and non-action of normal sleepers in response to a smoke detector alarm. Fire Saf J 25:125–13910.1016/0379-7112(95)00041-0 ↗
8. Bruck D, Brennan P (2001) Recognition of fire cues during sleep, Proceeding of the second international symposium on human behavior in fire. Interscience Communications, London, pp. 241–252
9. Bruck D, Ball M (2007) Optimizing emergency awakening to audible smoke alarms: an update. Hum Factors 49:585–60110.1518/001872007X215674 ↗
10. Bruck D, Thomas I (2008) Comparison of the effectiveness of different fire notification signals in sleeping older adults. Fire Technol 44:15–3810.1007/s10694-007-0017-5 ↗
11. Hasofer AM, Thomas IR (2007) Sound intensity required for waking up. Fire Saf J 42:265–27010.1016/j.firesaf.2006.11.005 ↗
12. Proulx G, Laroche C (2003) Recollection, identification and perceived urgency of the temporal-three evacuation signal. J Fire Prot Eng 13:67–8210.1177/1042391503013001004 ↗
13. Proulx G (2000) Strategies for ensuring appropriate occupant response to fire alarm signals, Construction Technology Update No.43, Institute for Research in Construction, National Research Council of Canada
14. Proulx G (2000) Why building occupants ignore fire alarms, Construction Technology Update No. 42. Institute for Research in Construction, National Research Council of Canada
15. Tong D, Canter D (1985) Informative warnings: in situ evaluations of fire alarms. Fire Saf J 9:267–27910.1016/0379-7112(85)90037-2 ↗
16. Kahn MJ (1984) Human awakening and subsequent identification of fire-related cues. Fire Technol 20:20–2610.1007/BF02390045 ↗
17. Otto N, Amman S, Eaton C, Lake S (2001) Guidelines for jury evaluations of automotive sounds. Sound and Vib 35(4):24–47
18. ISO 8201 (2017) Alarm systems—audible emergency evacuation signal—requirements
19. Haas EC, Edworthy J (1996) Designing urgency into auditory warnings using pitch, speed and loudness. Comp Cont Eng J 7:193–19810.1049/cce:19960407 ↗
20. Lee MJ, Lee KR, Kim MJ (2010) Evaluation on the improvement of the fire alarm sounder by the sound insulation in apartment buildings. In: The 39th international congress and exhibition on noise control engineering. Lisbon.
21. Lee MJ, Kim MJ (2018) Sound attenuation and audibility of fire alarm signal in Korean residential apartment buildings: a case study. Indoor Built Environ 27:690–70510.1177/1420326X16687108 ↗
22. Proulx G, Sime JD (1991) To prevent ‘panic’ in an underground emergency: why not tell people the truth?. In: Fire safety science-proceedings of the 3rd international symposium. Elsevier Applied Science, London, pp 843–85210.3801/IAFSS.FSS.3-843 ↗