Operating Experiences from Fire Sprinkler and Water Mist Installations in Swedish Churches
Source abstract
Abstract
Abstract During the past 20 years, the fire protection of ancient churches in Sweden has been improved with the installation of fire detection, fire sprinkler and water mist systems. The project identified 52 churches with either traditional sprinkler or high-pressure water mist systems. The operating experiences of these systems were documented by interviews with the end users, fire protection inspectors, system installers and by study visits. Problems associated with the use of antifreeze for water mist systems were identified. Systems have experienced leakage, high system pressures during warm days and corresponding unintentional activations due to breakage of nozzles or nozzle glass bulbs. For both sprinkler and water mist systems designed as dry-pipe systems, unintentional activations have occurred during wintertime due to freezing. Testing of dry-pipe systems also revealed unacceptably long water delivery times and residual water in piping. Many of the smaller rural churches are using a high-pressure gas- (nitrogen) driven pump because the public grid is unreliable. Three suffocation incidents were documented when nitrogen was unintentionally released into the confined technical space. Two of the incidents can be described as profoundly serious. For traditional dry-pipe systems galvanized pipes are often used but cases of internal pipe corrosion and leakage from pipes were documented. The church facility managers have a key role in the daily supervision of these installations. But it requires effort, technical competence and not least a substantial deal of self-interest. For some churches, high staff turnover has contributed to a lack of competence and supervision and maintenance has been neglected. High frequency of fault alarms (operating alarms) was also perceived as a burden and is also costly. Overall, the occurrence of technical problems and excessive costs have contributed to the shutdown or even dismantling of water mist systems in ten documented cases.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Fire dynamics and safety research
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (22)
Show source-provided references
1. Arvidson M (2008) Experience with fire suppression installations for wood churches in Sweden. J Fire Prot Eng 18(2):141–159. https://doi.org/10.1177/104239150708643110.1177/1042391507086431 ↗
2. ”De tretton stiften (’The thirteen dioceses’)”, www.svenskakyrkan.se/stiften Accessed 27 Dec 2023
3. “Svenska kyrkan i siffror (’The Swedish Church in numbers’)”, www.svenskakyrkan.se/statistik Accessed 27 Dec 2023
4. SS-EN 12845:2015, ”Brand och räddning—Fasta släcksystem—Automatiska sprinklersystem—Utförande, installation och underhåll (’Fixed firefighting systems—Automatic sprinkler systems—Design, installation and maintenance’)”, approved 2015–06–14, published 2015–06–16
5. SBF 120:8, ”Regler för automatiskt vattensprinklersystem 2016 (’Rules for automatic water sprinkler systems’)”, Brandskyddsföreningen, Stockholm
6. SS-EN 14972–1:2020, ”Fasta släcksystem—Vattendimsystem—Del 1: Utförande, installation, kontroll och underhåll (’Fixed firefighting systems—Water mist systems—Part 1: Design, installation, inspection and maintenance’)”, edition 1, approved: 2020–12–28
7. SBF 503:2, 2023 ”Regler för vattendimsystem (’Rules for water mist systems’)”, Brandskyddsföreningen, Stockholm
8. SIS-CEN/TS 14972:2008, Fixed firefighting systems—Watermist systems—Design and installation, edition 1, published on 2008–06–26
9. SIS-CEN/TS 14972:2011, Fixed firefighting systems—Watermist systems—and installation, edition 2, published on 2011–12–28
10. SBF 503:1, 2019 ”Regler för vattendimsystem (’Rules for water mist systems’)”, Brandskyddsföreningen, Stockholm
11. ”Sveriges klimat” (”Sweden's climate), https://sv.wikipedia.org/wiki/Sveriges_klimat Accessed 3 Jan 2025
12. ”Årets och årstidernas väder och vatten (’ Weather and water of the year and seasons’)”, https://www.smhi.se/klimat/klimatet-da-och-nu/arets-vader Accessed 3 Jan 2025
13. Fransson S, 2023 “Sprinklersystem för brandsläckning i Karlstad stift (‘Sprinkler systems for fire-fighting in Karlstad diocese’)”, Svenska kyrkan, Karlstad
14. Nilsson I (2018) Rapport avseende vattenskada (Report regarding water damage). Polygon Sverige AB
15. ”Insatsrapport från räddningstjänsten” (‘Action report from the rescue service’)”, January 29, 2011
16. Rudérus H (2014) Kyrkan, historik och beskrivning (The church, history and description)
17. Personal communication with the cemetery and facility managers of the church on November 27, 2023
18. Personal communication with Tomas Godby on November 20, 2023
19. Arvidson M (2014) Släcksystem med vattendimma—en förnyad kunskapssammanställning, Brandforsk projekt 500–121 (’Water mist fire protection systems - a renewed compilation of knowledge, Brandforsk project 500–121’). SP Rapport 2014:30
20. Kochelek TJ, Kirn L (2011) Six Reasons Why Galvanized Steel Piping Should NOT be Used in Dry and Preaction Fire Sprinkler Systems. Engineered Corrosion Solutions, LLC
21. Lindsten J (2011) Flicka dog efter olycka på kyrkogård (’Girl died after accident in cemetery’). Borås Tidning
22. Arvidson M, Egeltoft E, Godby T (2023) Driftserfarenheter från sprinklerinstallationer i kyrkor och andra kulturhistoriskt värdefulla byggnader Brandforsk projekt 323–010” (’Operating experiences from sprinkler system installations in Swedish churches and other heritage buildings’). RISE Rapport 2023:133, ISBN: 978–91–89896–20–8, RISE Research Institutes of Sweden