Electromagnetic-Thermal-Flow Field Coupling Simulation of 12-kV Medium-Voltage Switchgear
Source abstract
Abstract
Long-term heating and excessive temperature rise will significantly affect the electrical and insulation performance of electric power equipment, causing the potential security risk. In this paper, the temperature rise situation under normal operation of a 12-kV medium voltage switchgear is studied through modeling and simulation method. First, in the simulation analysis of the whole switchgear, based on the theory of eddy-current field, gas flow field, and temperature field, the temperature rise distribution of the switchgear under the condition of natural convection and forced convection is simulated and analyzed. Then, several improvement methods are taken to reduce the temperature rise that emerges in the switchgear, including using spring contact finger structure to replace flexible connection structure, and also the optimization scheme of vacuum circuit breaker (VCB) pole and current transformer (CT). Then, simulation and research of different improvement schemes are conducted based on the electromagnetic-thermal-flow field coupling method. The simulation results of whole switchgear show that the above coupling method is very useful for the calculation of temperature rise. The simulation results also show that the spring contact structure is beneficial to reduce the temperature rise of vacuum interrupter and mechanical connection part. After the modification of design, the temperature rise conditions of the VCB pole and CT are significantly improved.
Source: openalex_inverted_index · Quality: baseline
Research context
OpenAlex topics: Thermal Analysis in Power Transmission · Vacuum and Plasma Arcs · High voltage insulation and dielectric phenomena
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (11)
Show source-provided references
1. Design and analysis of new type air-core reactor based on coupled fluid-thermal field calculation
2. 10.1109/TCPMT.2015.239619710.1109/TCPMT.2015.2396197 ↗
3. Ansys Fluent 15 0 Help Document · 2012
4. A novel approach for the thermal analysis of air insulated switchgear
5. Simulation of electrical field and breakdown phenomena in low voltage circuit breakers
6. Analysis of thermal capacity for busbar trunking system by coupled magneto-fluid-thermal field calculation
7. Ansys Maxwell 16 0 Help Document · 2012
8. Dynamic thermal simulation of gas insulated switchgear
9. 10.1109/TCAPT.2007.90628810.1109/TCAPT.2007.906288 ↗
10. 10.1109/TMAG.1983.106281910.1109/TMAG.1983.1062819 ↗
11. 10.1109/TCAPT.2002.80460810.1109/TCAPT.2002.804608 ↗