Chip to Chiller Experimental Cooling Failure Analysis of Data Centers: The Interaction Between IT and Facility
Source abstract
Abstract
Cooling failure in data centers (DCs) is a complex phenomenon due to the many interactions between the cooling infrastructure and the information technology equipment (IT). To fully understand it, a system integration philosophy is vital to the testing and design of experiment. In this paper, a facility-level DC cooling failure experiment is run and analyzed. An airside cooling failure is introduced to the facility during two different cooling set points as well as in open and contained environments. Quantitative instrumentation includes pressure differentials, tile airflow, external contour and discrete air inlet temperature, intelligent platform management interface (IPMI), and cooling system data during failure recovery. Qualitative measurements include infrared imaging and airflow visualization via smoke trace. To our knowledge of current literature, this is the first experimental study in which an actual multi-aisle facility cooling failure is run with real IT (compute, network, and storage) load in the white space. This will establish a link between variations from the facility to the central processing unit (CPU). The results show that using the external IT inlet temperature sensors, the containment configuration shows a longer available uptime (AU) during failure. However, the IPMI data show the opposite. In fact, the available uptime is reduced significantly when the external sensors are compared to internal IT analytics. The response of the IT power, CPU temperature, and fan speed shows higher values during the containment failure. This occurs because of the instantaneous formation of external impedances in the containment during failure, which renders the contained aisle to be less resilient than the open aisle. The tradeoffs between PUE, OPEX, and AU are also explained.
Source: openalex_inverted_index · Quality: baseline
Research context
OpenAlex topics: Cloud Computing and Resource Management · Parallel Computing and Optimization Techniques · Advanced Data Storage Technologies
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (23)
Show source-provided references
1. 10.1115/1.400327410.1115/1.4003274 ↗
2. 10.1109/SEMI-THERM.2015.710013010.1109/SEMI-THERM.2015.7100130 ↗
3. 10.1115/InterPACK2009-8935910.1115/InterPACK2009-89359 ↗
4. 10.1109/TCPMT.2015.250845310.1109/TCPMT.2015.2508453 ↗
5. 10.1109/ITHERM.2014.689236210.1109/ITHERM.2014.6892362 ↗
6. 10.1109/SEMI-THERM.2015.710015710.1109/SEMI-THERM.2015.7100157 ↗
7. 10.1115/IPACK2015-4823410.1115/IPACK2015-48234 ↗
8. Experimental characterization of a rear door heat exchanger with localized containmentm
9. 10.1109/SEMI-THERM.2016.745846310.1109/SEMI-THERM.2016.7458463 ↗
10. stachecki · Short-Term Load Prediction and Energy-Aware Load Balancing for Data Centers Serving Online Requests · 0
11. demetriou · Effectively Applying the Expanded ASHRAE Guidelines in Your Data Center · 2015
12. 2013–2016 Cost of Data Center Outages Research Dept · 2016
13. 10.1109/TCAPT.2008.92362910.1109/TCAPT.2008.923629 ↗
14. 10.1109/ITHERM.2008.454439010.1109/ITHERM.2008.4544390 ↗
15. 10.1115/1.400711010.1115/1.4007110 ↗
16. 10.1115/1.400774410.1115/1.4007744 ↗
17. Data Center Outages Incidents and Industry Transparency · 2016
18. 10.1115/IPACK2013-7321910.1115/IPACK2013-73219 ↗
19. 10.1115/1.400465710.1115/1.4004657 ↗
20. Making scheduling ‘cool’: Temperature-aware workload placement in data centers
21. cengel · Thermodynamics An Engineering Approach · 2002 · 5
22. 10.1115/IMECE2015-5078210.1115/IMECE2015-50782 ↗
23. cengel · Heat Transfer A Practical Approach · 1998 · 141