Performance and Diagnosis of Aluminum Connectors Tested Inside MV Cable Splices
Source abstract
Abstract
Performance of power cable connectors is usually evaluated under bare conditions as for overhead applications, such as specified in the test standards ANSI C119.4 and IEC 61238-1. Significant differences exist between the requirements of these two standards, in particular, the short-circuit current test that only becomes optional in the recent ANSI 2011 edition. Furthermore, past and recent experience with testing medium-voltage cable splices according to the standard IEEE 404 have revealed the shortcoming of the aluminum connectors tested on aluminum conductors with overheating failure. New mechanical power connectors on the market offering range-taking capability and easy installation promise better connectivity and reproducibility based on the shear-bolt technology. This paper discusses the results as obtained in an accelerated aging test on different types of cable splices with both compression and mechanical connectors. Based on the test results, a simple and effective method is also proposed to identify a degraded connector inside a cable splice.
Source: openalex_inverted_index · Quality: baseline
Research context
OpenAlex topics: Electrical Contact Performance and Analysis · Electrical Fault Detection and Protection · Electronic Packaging and Soldering Technologies
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (23)
Show source-provided references
1. Impact of filled-strand conductor on connector temperatures for medium voltage joints
2. 10.1109/TPWRD.2004.82994610.1109/TPWRD.2004.829946 ↗
3. 10.1109/TPWRD.2007.91610110.1109/TPWRD.2007.916101 ↗
4. Compression and Mechanical Connectors for Power Cables for Rated Voltages up to 30 kV (Um=36 kV)—Part 1 Test Methods and Requirements · 2003
5. 10.1109/IEEESTD.2016.759283810.1109/IEEESTD.2016.7592838 ↗
6. Overhead lines—Requirements and Tests for Fittings · 1997
7. Short-circuit performance of metallic shielding and sheaths of insulated cables · 2017
8. 10.1049/cp.2013.057210.1049/cp.2013.0572 ↗
9. An effective-resistance measurement technique for improving the current-cycling test of power connectors
10. 10.1109/HOLM.2004.135310110.1109/HOLM.2004.1353101 ↗
11. 10.1109/TPWRD.1987.430815910.1109/TPWRD.1987.4308159 ↗
12. Mechanical connectors used inside M.V. Accessories: A system approach
13. The need to update/upgrade test procedures for connectors used in MV underground joints
14. 10.1109/ELINSL.1990.10975210.1109/ELINSL.1990.109752 ↗
15. 10.1109/IEEESTD.2012.622022510.1109/IEEESTD.2012.6220225 ↗
16. American National Standard for Electric Connectors—Connectors for Use Between Aluminum-to-Aluminum and Aluminum-to-Copper Conductors Designed for Normal Operation at or Below 93 °C and Copper-to-Copper · 2016
17. 10.1049/cp:2005094510.1049/cp:20050945 ↗
18. 10.1109/28.12672910.1109/28.126729 ↗
19. 10.1109/TPWRD.2004.82991710.1109/TPWRD.2004.829917 ↗
20. 10.1109/TIA.1983.450422010.1109/TIA.1983.4504220 ↗
21. 10.1049/cp:2001072610.1049/cp:20010726 ↗
22. 10.1109/TIA.2017.265500810.1109/TIA.2017.2655008 ↗
23. Steady one-dimensional systems