journal article·2026

Study on the Effect of Liquid-Bridge Molten-Pool Pre-Damage on Electrical Erosion of Air-Circuit-Breaker Contacts Under Oxidation Kinetics

J. Li, Y. Wang, W. Duan, S. Fu, C. Huang, Z. Li

Publisher page

Abstract

Electrical erosion is the primary cause of end-of-life failure in circuit-breaker contacts. In air, erosion develops continuously from the liquid-bridge stage to the arc stage, involving oxygen-assisted electrochemical reactions and strong multiphysics coupling. This work establishes a continuous mathematical model to quantify how liquid-bridge pre-damage influences subsequent arc erosion. A modified level-set method is coupled with oxidation-kinetics equations to capture contact melting and erosion under arc interaction in an oxygen environment. The results indicate that, under high arc power, oxygen substantially lowers the surface-tension coefficient of molten copper through oxidation kinetics, which strengthens Marangoni-driven radial flow and increases both crater width and depth. After bridge rupture, the residual liquid-bridge molten-pool markedly changes the thermoelectric and mechanical boundary conditions. This produces a thermal deposition effect, redistributes arc forces, and promotes a W-shaped melt-pool profile accompanied by strong central droplet ejection. Across the investigated power range, the simulations reveal a consistent trend: at relatively low arc powers, the initial melt-pool geometry and thermal history from the liquid-bridge stage noticeably affect later erosion, whereas at higher arc powers the process is increasingly governed by rapid evaporation and splash-controlled removal. As a result, the influence of micrometer-scale pre-damage is progressively masked by the overall arc thermodynamics. These findings support contact-lifetime prediction and guide the optimization of air-switch contacts over different power levels, contributing to higher-accuracy electrical-life models. And the modeling framework developed in this work is material-agnostic at the methodological level and provides a transferable research route for extending arc-erosion analysis to other contact materials.
Source: openalex_inverted_index · Quality: baseline

Research context

OpenAlex topics: Electrical Contact Performance and Analysis · Vacuum and Plasma Arcs · Advanced Surface Polishing Techniques

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

School of Electrical Engineering, Key Laboratory of Special Machines and High Voltage Apparatus, Shenyang University of Technology, Shenyang, China

Funding

National Natural Science Foundation of China

References

Reference metadata was not supplied for this record.