Application of adsorption technique in the estimation of drift losses through the cooling towers

P. V. Joshi, S. D. Bedekar, Pratap V Nair, S. B. War, Shubang Vyas, R.P. Saini

Open full text

Abstract

Adsorption technique has been used in the estimation of drift losses through the cooling towers of Central Airconditioning Plant (CAP), BARC. CAP uses two types of drift eliminators for minimising the drift losses. Using molecular sieves as adsorbent, the efficiency of eliminator I and eliminator II was estimated to be 80.12 and 99.25% respectively. The additional water saving due to the use of eliminator II instead of eliminator I is estimated to be 59.28 m 3 per day.