Performance comparison of liquid, vapor, and liquid–vapor injection of single-screw compressor for an air-source heat pump
Source abstract
Abstract
Refrigerant injection techniques are usually proposed to improve the performance and reliability of compressors when a single-screw compressor applied to an air-source heat pump works at low temperatures in winter. In this study, an experimental study was conducted to present the performance comparison of the single-screw compressor in the air-source heat pump under liquid, vapor, and liquid–vapor refrigerant injection at evaporation temperatures between −19 and −8 °C. The results indicate that, when the evaporation temperature decreases from −8 to −19 °C, the heating capacity under liquid–vapor and vapor injection increases by 16.7% and 12.7%, respectively, compared with that under liquid injection and that the COPh increment under liquid–vapor injection and vapor injection is, respectively, from 11.23% to 39.21% and from 17.18% to 30.82% compared with that under liquid injection. Therefore, the liquid–vapor injection method is conducive to the operation of the air-source heat pump at a lower ambient temperature. The experimental results can provide the basis for the future design of single-screw compressors applied to air-source heat pumps.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Refrigeration and Air Conditioning Technologies · Building Energy and Comfort Optimization · Heat Transfer and Optimization
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Huadian Electric Power Research Institute Co., Ltd. 1 , Hangzhou 310030, China
MOE Key Laboratory of Enhanced Heat Transfer and Energy Conservation, Beijing University of Technology 2 , Beijing 100124, China
Beijing Key Laboratory of Heat Transfer and Energy Conversion, Beijing University of Technology 3 , Beijing 100124, China
Funding
Beijing Municipal Education Commission · Scientific and Technological Project of Henan Province
References (29)
Show source-provided references
1. A review of technology and policy deep decarbonization pathway options for making energy-intensive industry production consistent with the Paris Agreement10.1016/j.jclepro.2018.03.107 ↗
2. Heat pumps and our low-carbon future: A comprehensive review10.1016/j.erss.2020.101764 ↗
3. The future of low carbon industrial process heat: A comparison between solar thermal and heat pumps10.1016/j.solener.2018.08.011 ↗
4. Experimental exergy and energy analysis of a novel high-temperature heat pump with scroll compressor for waste heat recovery10.1016/j.apenergy.2019.113504 ↗
5. Performance of a single-stage recuperative high-temperature air source heat pump10.1016/j.applthermaleng.2021.116969 ↗
6. Air source heat pumps field studies: A systematic literature review10.1016/j.rser.2020.110275 ↗
7. Thermodynamic analysis of single-stage compression air-source heat pumps with different recuperation ways for large temperature lift10.1016/j.ijrefrig.2019.09.006 ↗
8. Performance investigation of vapor and liquid injection on a refrigeration system operating at high compression ratio10.1016/j.ijrefrig.2015.01.013 ↗
9. Vapor refrigerant injection techniques for heat pump systems: The latest literature review and discussion10.1142/S201013251430002X ↗
10. Performance comparison among two-phase, liquid, and vapor injection heat pumps with a scroll compressor using R410A10.1016/j.applthermaleng.2018.03.086 ↗
11. Performance of a two-phase injection heat pump with the variation of injection quality and pressure10.1142/s2010132517500183 ↗
12. Numerical study on the optimal design of injection-hole geometries of a twin rotary compressor in a liquid injection heat pump10.1016/j.applthermaleng.2016.11.115 ↗
13. Experimental investigation on vapor injection heat pump with a newly designed twin rotary variable speed compressor for cold regions10.1016/j.ijrefrig.2015.10.024 ↗
14. Potential benefits of saturation cycle with two-phase refrigerant injection10.1016/j.applthermaleng.2013.03.030 ↗
15. Evaluation of two-phase suction, liquid injection and two-phase injection for decreasing the discharge temperature of the R32 scroll compressor10.1016/j.ijrefrig.2015.08.004 ↗
16. Modelica-based modeling and simulation of a twin screw compressor for heat pump applications10.1016/j.applthermaleng.2013.04.020 ↗
17. Performance optimization of a heat pump integrated with a single-screw refrigeration compressor with liquid refrigerant injection10.1016/j.energy.2020.118197 ↗
18. Simulation analysis of the performance of an air-source heat pump system with economizer based on single screw compressor10.11936/bjutxb2018080014 ↗
19. Worm rotary compressors with liquid joint
20. From water to refrigerant: Twenty years to develop the oil injection free single screw compressor
21. Refrigerant injection for heat pumping/air conditioning systems: Literature review and challenges discussions10.1016/j.ijrefrig.2010.09.015 ↗
22. Characterization of a vapor injection scroll compressor as a function of low, intermediate and high pressures and temperature conditions10.1016/j.ijrefrig.2013.04.022 ↗
23. Optimization of the injection-port geometries of a vapor injection scroll compressor based on SCOP under various climatic conditions10.1016/j.energy.2017.06.153 ↗
24. Optimization of refrigeration system with gas-injected scroll compressor10.1016/j.ijrefrig.2009.06.008 ↗
25. Influence of liquid refrigerant injection on the performance of an inverter-driven scroll compressor10.1016/s0140-7007(02)00017-8 ↗
26. 2008
27. Experimental study on p–V indicator diagrams of twin-screw refrigeration compressor with economizer10.1016/j.applthermaleng.2003.11.015 ↗
28. Experimental study on performance of air-cooled screw heat pump with flash tank economizer10.3969/j.issn.0253-4339.2013.05.055 ↗
29. Theoretical research and optimization analysis for the injection process of the single screw refrigeration compressor10.1016/j.ijrefrig.2017.12.003 ↗