Strengthening of Gulfport 230 kV Wooden Transmission Structures with Glass-Fiber-Reinforced Polymer Wrap
Source abstract
Abstract
This paper presents a statistically designed experimental program to present and analyze an effective and practical strengthening system for deteriorated crossarms of the Gulfport timber structures using glass-fiber-reinforced polymer (GFRP) wrap. In this research, a total of 14 strengthened and six control specimens with a length of approximately 3.1 m were tested to failure. The experimental program was conducted in two phases: feasibility study and parameter optimization designed by using the Taguchi method and analysis of variation (ANOVA). The feasibility study concluded that the proposed strengthening system was sufficient for increasing the strength of the deteriorated crossarms of the Gulfport structures well above the critical end-of-life (EOL) design threshold value of the crossarms. The parametric optimization of the strengthening system identified the critical variables to be the crack-repair material, the width of the wrap, and sanding the surface. Using statistical advantages of the Taguchi method of experimental design, the mean strength of the strengthened specimens was estimated, and a 95% confidence interval for that mean was calculated. This estimated mean was 70% higher than the EOL threshold of the crossarms.
Source: openalex_inverted_index · Quality: baseline
Research context
OpenAlex topics: Structural Behavior of Reinforced Concrete · Structural Response to Dynamic Loads · Innovative concrete reinforcement materials
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Ph.D. Candidate, Dept. of Civil and Environmental Engineering, Univ. of Waterloo, Waterloo, ON, Canada.
Associate Professor, Dept. of Civil and Environmental Engineering, Univ. of Waterloo, Waterloo, ON, Canada (corresponding author).
Professor/NSERC-UNENE Chair, Dept. of Civil and Environmental Engineering, Univ. of Waterloo, Waterloo, ON, Canada.
References (17)
Show source-provided references
1. 10.1177/073168440504489810.1177/0731684405044898 ↗
2. American Concrete Institute (ACI). (2007). “Report on fiber-reinforced polymer (FRP) reinforcement for concrete structures.” ACI 440R-07 Farmington Hills MI.
3. Bendell A. · 1989
4. 10.1061/(ASCE)1090-0268(2001)5:1(3)10.1061/(ASCE)1090-0268(2001)5:1(3) ↗
5. 10.1016/j.compositesb.2004.04.01310.1016/j.compositesb.2004.04.013 ↗
6. Canadian Standards Association (CSA). (2001). CSA C22.3 No. 1-01 Overhead Systems Toronto.
7. 10.1061/(ASCE)1090-0268(2006)10:3(234)10.1061/(ASCE)1090-0268(2006)10:3(234) ↗
8. 10.1520/CTR10544J10.1520/CTR10544J ↗
9. 10.1520/CTR10545J10.1520/CTR10545J ↗
10. 10.1061/(ASCE)1090-0268(1999)3:2(92)10.1061/(ASCE)1090-0268(1999)3:2(92) ↗
11. 10.1177/07316840303558310.1177/073168403035583 ↗
12. Institute of Electrical and Electronics Engineers (IEEE). (1993). National Electrical Safety Code (NESC) C2-1993 New York.
13. McCarthy F. J. (2005). “Condition assessment of wooden crossarms in 230 KV transmission structures.” M.Sc. thesis Univ. of Waterloo Waterloo ON Canada.
14. 10.1016/0950-0618(95)00021-710.1016/0950-0618(95)00021-7 ↗
15. Shahi A. (2008). “Strengthening of wooden crossarms in 230 kV transmission structures using glass fiber reinforced polymer (GFRP) wrap.” M.Sc. thesis Univ. of Waterloo Waterloo ON Canada.
16. Sika · 2008
17. Sika · 2009