Use of a Time Constant for Designing a Smoke Control System in Car Parks
Source abstract
Abstract
The fire environment in thirty-six car parks of volumes varying from 2,000 m 3 to 50,000 m 3 , ceiling heights of 3 m, 4 m and 5 m are simulated using the fire zone model, CFAST version 2.0 developed at the Building and Fire Research Laboratory, NIST in U.S.A. The concept of using the space volume as a criterion to determine the requirement of smoke extraction system is reviewed. The concept of time constant in an atrium hall is proposed to be used in car parks and underground spaces. The empirical expression fitted by experimental data appearing in NFPA-92B is applied to calculate the time con stant. This is then correlated with the smoke filling time for those thirty-six car parks with and without natural horizontal ceiling vents. Design of the smoke extraction system for underground spaces is also studied.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Fire dynamics and safety research · Evacuation and Crowd Dynamics · Education, Safety, and Science Studies
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Department of Building Services Engineering The Hong Kong Polytechnic University Hung Hom, Kowloon Hong Kong
References (22)
Show source-provided references
1. Chow, W.K. · Tunnelling and Underground Space Technology · 1990
2. 1990
3. Morgan, H.P. · 1990
4. Klote, J. · 1992
5. Butcher, E.G. · 1970
6. Bennetts, I.D. · 1990
7. Chow, W.K. · Journal of Fire Protection Engineering · 1995
8. Peacock, R.D. · 1993
9. 10.1177/07349041930110020610.1177/073490419301100206 ↗
10. Cooper, L.Y. · 1990
11. Forney, G.P. · 1990
12. Cooper, L.Y. · 1990
13. Forney, G.P. · 1990
14. 1990
15. 10.1002/fam.81018050810.1002/fam.810180508 ↗
16. Chow, W.K.
17. Thomas, P.H. · 1963
18. Zukoski, E.E. · Fire Safety Journal · 1980 · 3 · 107
19. 1991
20. Klote, J.H. · 1994
21. Söderbom, J. · 1992
22. Chow, W.K. · Fire Safety Science-in Chinese · 1993 · 2 · 60