journal article·2008-03

Transient Ceiling Jet Temperature and Velocity Profiles in the Presence of an Upper Layer: Comparison with Predictions by LAVENT and JET Computer Fire Models

Vahid Motevalli, Siamak Riahi

Journal of Fire Sciences· Volume 26· Issue 2
Publisher page

Abstract

Results of a scaled experimental study are compared with the predictions produced by the LAVENT and JET computer fire models. As in most large-scale fire testing, characterization of heat release rate (HRR) and accuracy of its measurement creates a lot of uncertainty for validation of these codes. Sensitivity of LAVENT results to the assumed radiative loss of 35% is examined by varying the total HRR which corresponds to varying the convective HRR. Comparisons show that LAVENT uses the wall-jet theory at its core for prediction of the ceiling jet flow and thus does not capture the ceiling jet profile well and overpredicts the upper layer temperature during the development of the layer. The velocity is generally overpredicted since the retardation of the jet momentum by the upper layer does not seem to be modeled accurately. JET has a better user interface and slightly different parameters, but does not provide ceiling jet profiles. The major difference between JET and LAVENT include the ceiling jet temperature and velocity algorithms, the fusible link algorithms, and the use of a variable radiative fraction as a function of fire size and type.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Fire dynamics and safety research · Fire effects on ecosystems · Evacuation and Crowd Dynamics

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Department of Civil and Environmental Engineering The School of Engineering and Applied Science The George Washington University, 20101 Academic Way Ashburn, VA 20147, USA,

Department of Civil and Environmental Engineering The School of Engineering and Applied Science The George Washington University, 20101 Academic Way Ashburn, VA 20147, USA

References (23)

Show source-provided references
1. 10.1007/BF0103932410.1007/BF01039324 ↗
2. 10.1016/0379-7112(90)90030-I10.1016/0379-7112(90)90030-I ↗
3. 10.6028/NIST.IR.89-412210.6028/NIST.IR.89-4122 ↗
4. 10.1007/BF0147086310.1007/BF01470863 ↗
5. Davis, W.D. (1991). The Zone Fire Model Jet: A Model for the Prediction of Detector Activation and Gas Temperature in the Presence of a Smoke Layer, Nat'l Institute of Standards and Technology, Report No. NISTIR 6324.
6. Motevalli, V. · 1989
7. 10.1007/BF0259054310.1007/BF02590543 ↗
8. Heskestad, G.
9. 10.1115/1.324511310.1115/1.3245113 ↗
10. Motevalli, V.
11. 10.1007/BF0238416310.1007/BF02384163 ↗
12. Cooper, L.Y.
13. 10.1016/0379-7112(81)90037-010.1016/0379-7112(81)90037-0 ↗
14. Motevalli, V. and Ricciuti, C. (1992). Characterization of the Confined Ceiling Jet in the Presence of an Upper Layer in Transient and Steady-state Conditions, National Institute of Standards and Technology , NIST-CGR-92-613, pp. 1—134.
15. Motevalli, V. · 1990
16. 10.1115/1.291128010.1115/1.2911280 ↗
17. 10.1016/0010-2180(77)90021-910.1016/0010-2180(77)90021-9 ↗
18. 10.1177/10423915900020020110.1177/104239159000200201 ↗
19. 10.1007/BF0247958310.1007/BF02479583 ↗
20. Woodhouse, A.
21. Holman, J.P. · 1990
22. Veldman, C.C. · Unobstructed Ceiling, National Bureau of Standard · 1977
23. 10.1080/0010220880892401410.1080/00102208808924014 ↗